Printed values, calculations, image traces and observed counts are different kinds of evidence. “Verified” applies to the specific reading—not to the whole room or model.
services1014y-img1331-heating-note-assemblyverified · printed
radiator_tube_count_default
ALL RADIATORS ON THIS FLOOR TO BE 3 TUBE3 count
Printed tube count per radiator under general floor rule; not installed radiator quantity.
IMG_1331 · Locate on drawing ↗Drawing notation: ALL RADIATORS ON THIS FLOOR TO BE 3 TUBE
Printed tube count per radiator under general floor rule; not installed radiator quantity.
services1014y-img1331-heating-note-assemblyverified · printed
radiator_height_default
20″ HIGH UNLESS OTHERWISE NOTED20 in
Printed radiator-height default with explicit inch mark and exception retained.
IMG_1331 · Locate on drawing ↗Drawing notation: 20″ HIGH UNLESS OTHERWISE NOTED
Printed radiator-height default with explicit inch mark and exception retained.
services1014y-img1331-heating-note-assemblyverified · printed
radiator_connection_wall_relationship
ALL RADIATOR CONNECTIONS SHALL BE BROUGHT THRU WALL WHERE POSSIBLEConditional connection route requirement only; no wall penetration locations established.
IMG_1331 · Locate on drawing ↗Drawing notation: ALL RADIATOR CONNECTIONS SHALL BE BROUGHT THRU WALL WHERE POSSIBLE
Conditional connection route requirement only; no wall penetration locations established.
services1014y-img1331-heating-note-assemblyverified · printed
boot_material
ALL GALVANIZED IRON BOOTS FOR COPPER RADIATORS IN HEATING CONTRACTMaterial assigned only to boots; no sheet-metal thickness inferred.
IMG_1331 · Locate on drawing ↗Drawing notation: ALL GALVANIZED IRON BOOTS FOR COPPER RADIATORS IN HEATING CONTRACT
Material assigned only to boots; no sheet-metal thickness inferred.
services1014y-img1331-heating-note-assemblyverified · printed
radiator_material_in_boot_clause
ALL GALVANIZED IRON BOOTS FOR COPPER RADIATORS IN HEATING CONTRACTCopper applies to radiators named in the boot clause, not automatically every radiator on the floor.
IMG_1331 · Locate on drawing ↗Drawing notation: ALL GALVANIZED IRON BOOTS FOR COPPER RADIATORS IN HEATING CONTRACT
Copper applies to radiators named in the boot clause, not automatically every radiator on the floor.
services1014y-img1331-heating-note-assemblyverified · printed
boot_contract_scope
ALL GALVANIZED IRON BOOTS FOR COPPER RADIATORS IN HEATING CONTRACTPrinted contract allocation, not installation evidence.
IMG_1331 · Locate on drawing ↗Drawing notation: ALL GALVANIZED IRON BOOTS FOR COPPER RADIATORS IN HEATING CONTRACT
Printed contract allocation, not installation evidence.
services1014y-img1331-heating-note-assemblyverified · printed
steam_drop_riser_valve_requirement
VALVE ALL STEAM DROP RISERS AT TOP AND BOTTOMValve requirement for steam drop risers only.
services1014y-img1331-heating-note-assemblyverified · printed
steam_drop_riser_valve_locations
VALVE ALL STEAM DROP RISERS AT TOP AND BOTTOMLocations relative to each applicable riser; no exact heights or valve sizes established.
IMG_1331 · Locate on drawing ↗Drawing notation: VALVE ALL STEAM DROP RISERS AT TOP AND BOTTOM
Locations relative to each applicable riser; no exact heights or valve sizes established.
services1014y-img1331-heating-note-assemblyillegible · printed
return_riser_drip_default_size_unresolved
ALL RETURN RISERS AND RISER DRIPS TO BE [fraction unclear] UNLESS OTHERWISE NOTEDNumeric value unresolved
Fraction and its unit mark not securely distinguished. Preserve null; no size transfer from other floor or source.
IMG_1331 · Locate on drawing ↗Drawing notation: ALL RETURN RISERS AND RISER DRIPS TO BE [fraction unclear] UNLESS OTHERWISE NOTED
Fraction and its unit mark not securely distinguished. Preserve null; no size transfer from other floor or source.
services1014y-img1331-heating-note-assemblyverified · printed
return_runout_default_size
ALL RETURN RUNOUTS TO BE 1″1 in
Explicit printed one-inch return-runout default; following UNLESS OTHERWISE NOTED qualification applies to sentence. Drip-runout fraction remains separate.
IMG_1331 · Locate on drawing ↗Drawing notation: ALL RETURN RUNOUTS TO BE 1″
Explicit printed one-inch return-runout default; following UNLESS OTHERWISE NOTED qualification applies to sentence. Drip-runout fraction remains separate.
services1014y-img1331-heating-note-assemblyillegible · printed
drip_runout_default_size_unresolved
AND DRIP RUNOUTS TO BE [fraction unclear] UNLESS OTHERWISE NOTEDNumeric value unresolved
Drip-runout fractional size and its unit mark unresolved; not supplied by neighboring one-inch return-runout value.
IMG_1331 · Locate on drawing ↗Drawing notation: AND DRIP RUNOUTS TO BE [fraction unclear] UNLESS OTHERWISE NOTED
Drip-runout fractional size and its unit mark unresolved; not supplied by neighboring one-inch return-runout value.
services1014y-img1331-heating-note-assemblyverified · printed
combination_trap_types
COMBINATION FLOAT AND THERMOSTATIC TRAPSLiteral combination-trap designation in legend clause; installed types and quantity not established.
IMG_1331 · Locate on drawing ↗Drawing notation: COMBINATION FLOAT AND THERMOSTATIC TRAPS
Literal combination-trap designation in legend clause; installed types and quantity not established.
services1014y-img1331-heating-note-assemblyverified · printed
combination_trap_valve_symbol_relationship
COMBINATION FLOAT AND THERMOSTATIC TRAPS WITH VALVED BYPASS INDICATED THUS [symbol]Exact legend clause specifies valved bypass. No installed instance count or additional piping topology inferred.
IMG_1331 · Locate on drawing ↗Drawing notation: COMBINATION FLOAT AND THERMOSTATIC TRAPS WITH VALVED BYPASS INDICATED THUS [symbol]
Exact legend clause specifies valved bypass. No installed instance count or additional piping topology inferred.
services1014y-img1331-heating-note-assemblyverified · printed
thermostatic_trap_symbol_legend
THERMOSTATIC TRAPS INDICATED THUS [symbol]Caption preserves separate thermostatic-trap convention; no installed quantities established.
IMG_1331 · Locate on drawing ↗Drawing notation: THERMOSTATIC TRAPS INDICATED THUS [symbol]
Caption preserves separate thermostatic-trap convention; no installed quantities established.