Gus J. SolomonUnited States Courthouse
← Back to the building1933 reconstruction · research preview

The measured building.

Every dimension belongs to an object and a drawing. Original room numbers, object marks, printed values and source regions stay together—even when the answer is unresolved.

Source photographs
464
Identified objects
4872
Verified printed values
12046
Disputed values
20

464 of 464 photographs have extraction records, containing 27,517 properties. Initial image review is not exhaustive extraction: 0 photographs have passed the full-region check. 66 numbered sheets are reconciled. Modeling and architectural registration are separate work; these counts do not establish a complete building.

Download the structured register (JSON)

Open the coordinated research model →

Clear filters
IMG_1330 · Folder 186

Plumbing And Heating

Original sheet identity has not yet been reconciled.

Extraction: Reviewed · extraction partial. Partial timed visual review: Partial catalogue/OCR-first then sequential <=1000px JPEG65 locator review of public/archive/drawings/complete-upright/IMG_1330.webp. IMG_1322 additionally has one 250x435 post-schedule crop. Regions normalized in unrotated access-image coordinates; rotationDegrees is clockwise correction. Selected evidence only, no full extraction/modeling. Partial timed visual review: 2026-10-11 remaining-region review. Prior queue, OCR and packages reused; ten sequential inspections total, confined to IMG_1329/1334/1336/1337. Normalized regions in unrotated complete-upright WebP. Research only; no accepted geometry or complete extraction. Partial timed visual review: OCR and prior package text review only this pass; no new visual verification. Partial timed visual review: Additive source-local review; normalized coordinates in unrotated 2200×1650 access WebP. Reuse previous verified records; no accepted geometry or complete extraction. Partial timed visual review: undefined Partial timed visual review: undefined Partial timed visual review: Bounded additive source review. Printed schedule quantities and source-local apparatus detail dimensions do not establish installed building geometry. Partial timed visual review: Basement plan right general-note crop only; architectural underlay not measured. Partial timed visual review: Source-local schedule, fabrication or connection evidence only; no installed geometry or architectural acceptance.

Unresolved extraction work
  • partial locator coverage; remaining individual beam/member sizes, schedules, fine fractions and dimensions outstanding
  • all notes, revisions, symbols, utility legends and companion details require reconciliation
  • historical instance locations, material grades, connection capacities and modeling checks missing
  • Remaining individual dimensions, service/member instances, schedules, material and connection details require source review.
  • Original/revised annotation authority and companion registrations remain unresolved.
  • Architectural geometry and installed quantities are not established by service underlays.
  • Individual service routes, pipe sizes, fixture identities and room registrations remain to be reviewed at source resolution.
  • Original/revised annotation authority and companion details unresolved.
  • No architectural outlines or model geometry inferred; modeling status unchecked.
  • Remaining individual dimensions, service instances, fine callouts and routes require source review.
  • Original/revised annotations, companion sheets and installed registration unresolved.
  • Architectural geometry and installed quantities are not established; model unchecked.
  • Return/drip fractions remain unreadable in earlier inspections; compound questions are not closed by the separate1in clause.
  • Other notes, equipment ratings, routes, revision authority and installation remain unchecked.
  • Governing original/revision authority and actual installation unresolved.
  • Architectural registration, room polygons, installed counts and physical routes unchecked.
  • Other regions, notes, schedules, callouts and companion details require review.
  • Full source-to-building registration, installed quantities and as-built correspondence remain unresolved.
  • Complete notes, schedules, callouts, margins and colored revision authority outside listed regions await review.
  • Extraction remains partial; modeling/checking unchecked. No irrecoverable evidence conclusion.
  • Return riser/drop/runout values
  • Individual services, sizes and routing
  • Boiler-room apparatus notes and companion assignments
  • Revision authority
  • Complete source-to-plan registration and installed-instance applicability remain unresolved.
  • Unreviewed sheet regions, notes, callouts, schedules and revision authority remain open.
  • Material grades, full profiles, connection capacities and independent modeling checks unresolved.

Download OCR observations (unverified)

Loading the selected drawing…

Scroll or pinch to inspect this drawing. Archival drawing photograph · Oregon Historical Society research collections.

Open source image separately ↗

19 matching properties

Printed values, calculations, image traces and observed counts are different kinds of evidence. “Verified” applies to the specific reading—not to the whole room or model.

parallel-img1330-plumbingverified · printed

assignment

BASEMENT & FOUNDATION PLAN PLUMBING AND HEATING

Selected visible source evidence only; partial review, applies to depicted assembly.

IMG_1330 · Locate on drawing ↗

Drawing notation: BASEMENT & FOUNDATION PLAN PLUMBING AND HEATING

Selected visible source evidence only; partial review, applies to depicted assembly.

parallel-img1330-plumbingverified · observed

routing

Piping runs around footing grid, branch connections and valve marks shown

Selected visible source evidence only; partial review, applies to depicted assembly.

IMG_1330 · Locate on drawing ↗

Drawing notation: Piping runs around footing grid, branch connections and valve marks shown

Selected visible source evidence only; partial review, applies to depicted assembly.

parallel-img1330-plumbingverified · printed

backwater_valve

BACK WATER VALVE

Selected visible source evidence only; partial review, applies to depicted assembly.

IMG_1330 · Locate on drawing ↗

Drawing notation: BACK WATER VALVE

Selected visible source evidence only; partial review, applies to depicted assembly.

parallel-img1330-plumbingunreviewed · printed

piping_sizes

Unresolved

Numeric value unresolved

Selected visible source evidence only; partial review, applies to depicted assembly.

IMG_1330 · Locate on drawing ↗

Selected visible source evidence only; partial review, applies to depicted assembly.

parallel-img1330-boilerverified · printed

room_assignment

BOILER ROOM

Selected visible source evidence only; partial review, applies to depicted assembly.

IMG_1330 · Locate on drawing ↗

Drawing notation: BOILER ROOM

Selected visible source evidence only; partial review, applies to depicted assembly.

parallel-img1330-boilerunreviewed · observed

boiler_equipment

Boiler-room equipment outlines and connections visible; quantities/types unverified

Selected visible source evidence only; partial review, applies to depicted assembly.

IMG_1330 · Locate on drawing ↗

Drawing notation: Boiler-room equipment outlines and connections visible; quantities/types unverified

Selected visible source evidence only; partial review, applies to depicted assembly.

detail-basement-service-legend-1330verified · printed

trap-symbol-relationship

THERMOSTATIC TRAP INDICATED THUS [symbol]

Trap legend caption legible; steam-riser/drain fine wording and fitting sizes unresolved. Symbol identifies a convention, not an installed trap count.

IMG_1330 · Locate on drawing ↗

Drawing notation: THERMOSTATIC TRAP INDICATED THUS [symbol]

Trap legend caption legible; steam-riser/drain fine wording and fitting sizes unresolved. Symbol identifies a convention, not an installed trap count.

detail-basement-service-legend-1330unresolved · printed

steam-riser-drain-rule

Unresolved

Trap legend caption legible; steam-riser/drain fine wording and fitting sizes unresolved. Symbol identifies a convention, not an installed trap count.

IMG_1330 · Locate on drawing ↗

Trap legend caption legible; steam-riser/drain fine wording and fitting sizes unresolved. Symbol identifies a convention, not an installed trap count.

detail-basement-boiler-room-local-1330unresolved · printed

floor-penetration-relationship

ALL THRU [following text unresolved]

Selected boiler-room region reviewed; outlines observed without deriving equipment identity, capacity, dimensions or installed count.

IMG_1330 · Locate on drawing ↗

Drawing notation: ALL THRU [following text unresolved]

Selected boiler-room region reviewed; outlines observed without deriving equipment identity, capacity, dimensions or installed count.

detail-basement-boiler-room-local-1330verified · observed

equipment-outline-relationship

Two rectangular boiler/equipment outlines connect to drawn service routes

Selected boiler-room region reviewed; outlines observed without deriving equipment identity, capacity, dimensions or installed count.

IMG_1330 · Locate on drawing ↗

Drawing notation: Two rectangular boiler/equipment outlines connect to drawn service routes

Selected boiler-room region reviewed; outlines observed without deriving equipment identity, capacity, dimensions or installed count.

servicenotes-img1330-basement-return-notesverified · printed

return_runout_default_size

ALL RETURN RUNOUTS TO BE 1″

1 in

Printed separate return-runout clause only, qualified UNLESS OTHERWISE NOTED. The adjacent fractional drip-runout size remains unreadable, so the earlier compound question is not closed.

IMG_1330 · Locate on drawing ↗

Drawing notation: ALL RETURN RUNOUTS TO BE 1″

Printed separate return-runout clause only, qualified UNLESS OTHERWISE NOTED. The adjacent fractional drip-runout size remains unreadable, so the earlier compound question is not closed.

servicenotes-img1330-basement-return-notesverified · printed

riser_drip_term

ALL RETURN RISERS AND RISER DRIPS

Exact named components in first return-note line. Verifies RISER DRIPS wording only; does not establish the blurred fraction or close the prior compound size question.

IMG_1330 · Locate on drawing ↗

Drawing notation: ALL RETURN RISERS AND RISER DRIPS

Exact named components in first return-note line. Verifies RISER DRIPS wording only; does not establish the blurred fraction or close the prior compound size question.

servicenotes-img1330-basement-return-notesverified · printed

trench_return_pipe_material

RETURN PIPING IN TRENCHES TO BE BRASS WITH BRASS FITTINGS

Material note specifically applies to return piping in trenches; does not assign material to other piping.

IMG_1330 · W-450 · Locate on drawing ↗

Drawing notation: RETURN PIPING IN TRENCHES TO BE BRASS WITH BRASS FITTINGS

Material note specifically applies to return piping in trenches; does not assign material to other piping.

servicenotes-img1330-basement-return-notesverified · printed

condensation_trap_valve_relationship

CONDENSATION FLOAT AND THERMOSTATIC TRAPS WITH VALVES SHOWN INDICATED THUS [symbol]

Legend states association between depicted trap symbols and valves; no installed trap quantity established.

IMG_1330 · W-450 · Locate on drawing ↗

Drawing notation: CONDENSATION FLOAT AND THERMOSTATIC TRAPS WITH VALVES SHOWN INDICATED THUS [symbol]

Legend states association between depicted trap symbols and valves; no installed trap quantity established.

servicenotes-img1330-basement-return-notesverified · printed

thermostatic_trap_symbol_relationship

THERMOSTATIC TRAPS INDICATED THUS [symbol]

Separate thermostatic-trap legend preserved; individual plan symbols not enumerated.

IMG_1330 · W-450 · Locate on drawing ↗

Drawing notation: THERMOSTATIC TRAPS INDICATED THUS [symbol]

Separate thermostatic-trap legend preserved; individual plan symbols not enumerated.

servicenotes-img1330-basement-return-notesunreviewed · printed

return_riser_and_drop_default_size

ALL RETURN RISERS AND [word unclear] DRIPS TO BE [fraction unclear] UNLESS OTHERWISE NOTED

Numeric value unresolved

Numeral is too blurred to normalize; retained separately from return runout note.

IMG_1330 · W-450 · Locate on drawing ↗

Drawing notation: ALL RETURN RISERS AND [word unclear] DRIPS TO BE [fraction unclear] UNLESS OTHERWISE NOTED

Numeral is too blurred to normalize; retained separately from return runout note.

servicenotes-img1330-basement-return-notesunreviewed · printed

return_runout_default_size

ALL RETURN RUNOUTS TO BE [size unclear] AND DRIP RUNOUTS TO BE [fraction unclear] UNLESS OTHERWISE NOTED

Numeric value unresolved

Runout and drip runout values require better source resolution; no numerical guesses normalized.

IMG_1330 · W-450 · Locate on drawing ↗

Drawing notation: ALL RETURN RUNOUTS TO BE [size unclear] AND DRIP RUNOUTS TO BE [fraction unclear] UNLESS OTHERWISE NOTED

Runout and drip runout values require better source resolution; no numerical guesses normalized.

detail-basement-boiler-room-local-1330illegible · printed

boiler_room_elevation_reread

ELEV.77.[remaining digits illegible]

Numeric value unresolved

Native room label under BOILER ROOM; numerical fraction and printed unit unreadable. No elevation adopted.

IMG_1330 · Locate on drawing ↗

Drawing notation: ELEV.77.[remaining digits illegible]

Native room label under BOILER ROOM; numerical fraction and printed unit unreadable. No elevation adopted.

detail-basement-boiler-room-local-1330illegible · printed

boiler_capacity_reread

BOILER [fine capacity annotation illegible]

Numeric value unresolved

Fine text inside boiler outlines remains blurred; no horsepower or installed quantity derived.

IMG_1330 · Locate on drawing ↗

Drawing notation: BOILER [fine capacity annotation illegible]

Fine text inside boiler outlines remains blurred; no horsepower or installed quantity derived.

View all source photographs →