Gus J. SolomonUnited States Courthouse
← Back to the building1933 reconstruction · research preview

The measured building.

Every dimension belongs to an object and a drawing. Original room numbers, object marks, printed values and source regions stay together—even when the answer is unresolved.

Source photographs
464
Identified objects
4872
Verified printed values
12046
Disputed values
20

464 of 464 photographs have extraction records, containing 27,517 properties. Initial image review is not exhaustive extraction: 0 photographs have passed the full-region check. 66 numbered sheets are reconciled. Modeling and architectural registration are separate work; these counts do not establish a complete building.

Download the structured register (JSON)

Open the coordinated research model →

Clear filters
IMG_1229 · Folder 190

Roof: Plan

Original sheet identity has not yet been reconciled.

Extraction: Reviewed · extraction partial. Partial timed visual review: Partial text-first sequential locator review using <=1000px JPEG derivative of public/archive/drawings/complete-upright/IMG_1229.webp. Access-image normalized regions before rotation; rotationDegrees is clockwise turn required for primary lettering. Locator coverage does not mean complete regional extraction. No modeling. Partial timed visual review: Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved. Partial timed visual review: undefined

Unresolved extraction work
  • full review of all regions, dimensions, schedules, callouts and notes
  • floor/object registration
  • cropped or faint evidence and companion sheets
  • Exact dimensions and witness endpoints not fully extracted
  • Companion-detail, revision and floor/room registration unresolved
  • All-region review and modeling acceptance incomplete
  • Full penthouse P-mark schedule; function of crossed and stepped symbols; remaining small wall/offset tokens.
  • Roof slopes, vents/drains and exact field applicability are not closed by these local dimensions.
  • Classified finished/rough/masonry/frame witness endpoints and physical source-to-plan registration remain unresolved.
  • Original versus revision authority, companion applicability and installed/as-built state remain unresolved.
  • Remaining source regions, notes, dimensions and complete coverage audit remain open; no geometry or architectural acceptance.

Download OCR observations (unverified)

Loading the selected drawing…

Scroll or pinch to inspect this drawing. Archival drawing photograph · Oregon Historical Society research collections.

Open source image separately ↗

30 matching properties

Printed values, calculations, image traces and observed counts are different kinds of evidence. “Verified” applies to the specific reading—not to the whole room or model.

parallel-img1229-assemblyverified · printed

roof_plan_label

ROOF PLAN

Selected legible source evidence; partial assembly-local scope.

IMG_1229 · Locate on drawing ↗

Drawing notation: ROOF PLAN

Selected legible source evidence; partial assembly-local scope.

parallel-img1229-assemblyverified · printed

roof_material

COMPOSITION ROOF

Selected legible source evidence; partial assembly-local scope.

IMG_1229 · Locate on drawing ↗

Drawing notation: COMPOSITION ROOF

Selected legible source evidence; partial assembly-local scope.

parallel-img1229-assemblyverified · printed

roof_gutter_material

COPPER GUTTER

Selected legible source evidence; partial assembly-local scope.

IMG_1229 · Locate on drawing ↗

Drawing notation: COPPER GUTTER

Selected legible source evidence; partial assembly-local scope.

parallel-img1229-assemblyverified · printed

roof_slope

PITCH

Selected legible source evidence; partial assembly-local scope.

IMG_1229 · Locate on drawing ↗

Drawing notation: PITCH

Selected legible source evidence; partial assembly-local scope.

parallel-img1229-assemblyverified · printed

vent_label

VENT

Selected legible source evidence; partial assembly-local scope.

IMG_1229 · Locate on drawing ↗

Drawing notation: VENT

Selected legible source evidence; partial assembly-local scope.

parallel-img1229-assemblyverified · printed

downspout

DOWN SPOUT

Selected legible source evidence; partial assembly-local scope.

IMG_1229 · Locate on drawing ↗

Drawing notation: DOWN SPOUT

Selected legible source evidence; partial assembly-local scope.

parallel-img1229-assemblyverified · printed

roof_room_plan_dimension

14'-0"

168 in

Selected legible source evidence; partial assembly-local scope.

IMG_1229 · Locate on drawing ↗

Drawing notation: 14'-0"

Selected legible source evidence; partial assembly-local scope.

parallel-img1229-assemblyunreviewed · printed

roof_details_reference

CORNICE DRAINS CONNECTED TO LEADER [fine sheet reference unresolved]

Unresolved locator reading; numeric value withheld.

IMG_1229 · Locate on drawing ↗

Drawing notation: CORNICE DRAINS CONNECTED TO LEADER [fine sheet reference unresolved]

Unresolved locator reading; numeric value withheld.

parallel-img1229-assemblyunreviewed · printed

remaining_roof_geometry

[slopes, drains/vent sizes, roof elevations and attic-room dimensions unresolved]

Numeric value unresolved

Unresolved locator reading; numeric value withheld.

IMG_1229 · Locate on drawing ↗

Drawing notation: [slopes, drains/vent sizes, roof elevations and attic-room dimensions unresolved]

Unresolved locator reading; numeric value withheld.

detail-facade-1229-roof-drainageverified · printed

cornice-drain-companion-reference

CORNICE DRAINS CONNECTED TO ROOF DRAINS - SEE SH'T 209

209 sheet-number

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

IMG_1229 · Locate on drawing ↗

Drawing notation: CORNICE DRAINS CONNECTED TO ROOF DRAINS - SEE SH'T 209

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

detail-facade-1229-roof-drainageverified · printed

court-coping-material

TERRA COTTA COPING

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

IMG_1229 · Locate on drawing ↗

Drawing notation: TERRA COTTA COPING

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

detail-facade-1229-roof-drainageverified · printed

circular-vent-diameter-west-lower

36" VENT

36 in

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

IMG_1229 · Locate on drawing ↗

Drawing notation: 36" VENT

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

detail-facade-1229-roof-drainageverified · printed

circular-vent-diameter-south-east

26" VENT

26 in

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

IMG_1229 · Locate on drawing ↗

Drawing notation: 26" VENT

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

detail-facade-1229-roof-drainageverified · printed

circular-vent-diameter-west-mid

18" VENT

18 in

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

IMG_1229 · Locate on drawing ↗

Drawing notation: 18" VENT

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

detail-facade-1229-roof-drainageverified · printed

circular-vent-diameter-west-upper

18" VENT

18 in

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

IMG_1229 · Locate on drawing ↗

Drawing notation: 18" VENT

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

detail-facade-1229-roof-drainageverified · printed

court-corner-drain-elevation

194.25

194.25 ft

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

IMG_1229 · Locate on drawing ↗

Drawing notation: 194.25

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

detail-facade-1229-penthouseverified · printed

west-horizontal-plan-segment

11'-2"

134 in

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

IMG_1229 · Locate on drawing ↗

Drawing notation: 11'-2"

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

detail-facade-1229-penthouseverified · printed

downspout-diameter

DOWN SPOUT 2"

2 in

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

IMG_1229 · Locate on drawing ↗

Drawing notation: DOWN SPOUT 2"

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

detail-facade-1229-penthouseverified · printed

roof-access-local-elevation

EL. 195.00

195 ft

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

IMG_1229 · Locate on drawing ↗

Drawing notation: EL. 195.00

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

detail-facade-1229-penthouseverified · printed

hose-label

FIRE HOSE

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

IMG_1229 · Locate on drawing ↗

Drawing notation: FIRE HOSE

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

detail-facade-1229-penthouseverified · printed

platform-material

CEM. PL.

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

IMG_1229 · Locate on drawing ↗

Drawing notation: CEM. PL.

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

detail-facade-1229-penthouseverified · printed

access-ladder-material

IRON LADDER

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

IMG_1229 · Locate on drawing ↗

Drawing notation: IRON LADDER

Source-local architectural evidence only; no physical registration, installed quantity or accepted geometry. Existing verified measurements omitted; conflicting locator readings preserved.

roofsection1014s-1229-south-offset-chainverified · printed

horizontal_offset

4′-5″

53 in

South dimension line from west outer reference to west penthouse wall witness. Printed 4′5″ retained as source-local offset; witness class is not accepted.

IMG_1229 · Locate on drawing ↗

Drawing notation: 4′-5″

South dimension line from west outer reference to west penthouse wall witness. Printed 4′5″ retained as source-local offset; witness class is not accepted.

roofsection1014s-1229-east-spanverified · printed

vertical_plan_span

14′-0″

168 in

East vertical chain between upper and lower penthouse boundary references. Distinct from previously recorded south horizontal 14′0″. No accepted clear/wall-face interpretation.

IMG_1229 · Locate on drawing ↗

Drawing notation: 14′-0″

East vertical chain between upper and lower penthouse boundary references. Distinct from previously recorded south horizontal 14′0″. No accepted clear/wall-face interpretation.

roofsection1014s-1229-crossed-rectangleverified · printed

first_dimension_token

3′-6″ × 3′-6″

42 in

The first printed dimension token beneath the central crossed rectangle. No object function or clear/rough edge class inferred.

IMG_1229 · Locate on drawing ↗

Drawing notation: 3′-6″ × 3′-6″

The first printed dimension token beneath the central crossed rectangle. No object function or clear/rough edge class inferred.

roofsection1014s-1229-crossed-rectangleverified · printed

second_dimension_token

3′-6″ × 3′-6″

42 in

The second printed dimension token beneath the central crossed rectangle. No object function or clear/rough edge class inferred.

IMG_1229 · Locate on drawing ↗

Drawing notation: 3′-6″ × 3′-6″

The second printed dimension token beneath the central crossed rectangle. No object function or clear/rough edge class inferred.

roofsection1014s-1229-stepped-symbolverified · printed

first_dimension_token

3′-6″ × 5′-6″

42 in

First token beside the eastern stepped symbol; width/height axis and clear/overall endpoints not accepted. Tight native crop rotated to read the vertical label.

IMG_1229 · Locate on drawing ↗

Drawing notation: 3′-6″ × 5′-6″

First token beside the eastern stepped symbol; width/height axis and clear/overall endpoints not accepted. Tight native crop rotated to read the vertical label.

roofsection1014s-1229-stepped-symbolverified · printed

second_dimension_token

3′-6″ × 5′-6″

66 in

Second token is 5′6″ in the rotated native crop. Separate from central 3′6″×3′6″ symbol; no geometry registration or fixture type inferred.

IMG_1229 · Locate on drawing ↗

Drawing notation: 3′-6″ × 5′-6″

Second token is 5′6″ in the rotated native crop. Separate from central 3′6″×3′6″ symbol; no geometry registration or fixture type inferred.

roofsection1014s-1229-door-symbolverified · printed

first_door_size_token

3′-0″ × 6′-0″

36 in

First foot/inch size token adjacent to swung door at top-right of penthouse; code is not accepted as rough/frame/clear dimension.

IMG_1229 · Locate on drawing ↗

Drawing notation: 3′-0″ × 6′-0″

First foot/inch size token adjacent to swung door at top-right of penthouse; code is not accepted as rough/frame/clear dimension.

roofsection1014s-1229-door-symbolverified · printed

second_door_size_token

3′-0″ × 6′-0″

72 in

Second foot/inch size token of the same doorway note; installed leaf/frame relationship and governing schedule unresolved.

IMG_1229 · Locate on drawing ↗

Drawing notation: 3′-0″ × 6′-0″

Second foot/inch size token of the same doorway note; installed leaf/frame relationship and governing schedule unresolved.