464 of 464 photographs have extraction records, containing 27,517 properties. Initial image review is not exhaustive extraction: 0 photographs have passed the full-region check. 66 numbered sheets are reconciled. Modeling and architectural registration are separate work; these counts do not establish a complete building.

Download the structured register (JSON)

Open the coordinated research model →

Clear filters
IMG_1346 · Folder 186

Plumbing

Original sheet identity has not yet been reconciled.

Extraction: Reviewed · extraction partial. Partial timed visual review: OCR/catalogue/existing reports searched before one sequential small JPEG65 locator. Actual clockwise reading rotation 270 degrees. Regions are normalized raw access-image coordinates before rotation. Partial, not fully extracted. Partial timed visual review: Text-first reuse of prior packages/OCR/queue only in this additive pass; no source image reopened. Partial timed visual review: Prior text evidence reused; source not reopened in this pass. Partial timed visual review: Source-local printed service callout or depicted fixture only; no whole-floor completeness, installed quantity or accepted architectural geometry. Partial timed visual review: Text-first reuse only; no image reopened in this pass. Partial timed visual review: Additive source-local extraction and exact canonical text crosswalk; zero fresh visual calls for images without inspection receipts. Full-page crosswalk rectangle is an index locator, not inspected-area or completeness evidence. Partial timed visual review: undefined Partial timed visual review: Additive source-local note review; no accepted geometry or physical identity merge. Partial timed visual review: undefined Partial timed visual review: Additive partial source-local review; no accepted geometry or installed state. Partial timed visual review: Text-only reuse of room442 branch: existing2in W/V,1in CW/HW,half-inch RC andthree-quarter gas retained; no duplicate properties. Partial timed visual review: Bounded source-local service evidence only; no physical coordinates, installed quantity or architectural release. Partial timed visual review: Additive service evidence only. Raw master coordinates, EXIF ignored, used for new measurements. Text-only images retain prior source orientation; no new visual coverage. Drawn symbol counts do not establish installed quantities or lighting fixture types.

Unresolved extraction work
  • Partial <=1000px JPEG65 locator review; fine dimensions, notes, equipment callouts and complete region review remain outstanding
  • Register physical fixtures, pipe/vent instances, quantities, materials and connections
  • MEP underlay not accepted exact room geometry; reconcile architectural companion plans
  • Preserve printed originals separately from colored annotations and approval/archive marks
  • Fourth-floor source is plumbing plan, not independent architectural dimensions
  • Complete service-instance topology and room registration remain unresolved.
  • Governing fixture/material schedules and revision authority remain unresolved.
  • All unvisited regions require source-resolution review; modeling/checking unchecked.
  • Unvisited regions, schedules, annotations and companion details still require source-resolution review.
  • Installed service-instance topology, material schedules, room registration and governing revision remain unresolved.
  • Modeling and checking remain unchecked.
  • Final radiator schedule inlet/vent/stud cell blank; shared-value intent remains unresolved.
  • Complete pipe/fixture instance tracing and connection topology; remaining numeric callouts outside targeted core
  • Fixture specification/material schedules and governing companion plumbing details
  • Room and architectural companion-plan registration; no accepted room geometry or installed state
  • Full note, annotation, revision and schedule reconciliation at master crop resolution
  • Trace complete service connections and associate with architectural rooms.
  • Resolve materials, fixture specifications and governing revision.
  • Unvisited annotations and companion details remain pending; modeling and checking unchecked.
  • Complete branch endpoints, riser continuity and architectural room registration remain unresolved.
  • Governing fixture key, apparatus specification, materials, finishes and installed quantities remain unresolved.
  • Original printed and colored revision authority and all unvisited notes/schedules/companion details remain partly unreviewed.
  • Extraction remains partial; modeling/checking unchecked; no accepted source-to-world coordinates or whole-building acceptance.
  • Text-only routing in this package: broad fixture/material/installation nulls lack a uniquely established witness; existing bounded branch readings reused. No duplicate fixture counting or fresh visual evidence.
  • Installed instances, governing issue, material/finish and source-to-building registration remain unresolved.
  • Unvisited notes, schedules, branches, revisions and companion details remain to review; no whole-source completion.
  • Extraction partial; modeling/checking unchecked; no authoring or architectural release.
  • Governing sanitary fixture key, product specifications, fixture-body material and finish remain unestablished; glyph shape does not establish fixture class.
  • Accepted architectural host faces, source-to-building registration, installed quantity and as-built correspondence remain unresolved.
  • Notes, schedules, callouts and revisions outside explicitly reviewed regions await source-resolution review; no irrecoverable evidence conclusion.
  • Extraction remains partial; modeling and checking unchecked.
  • Governing fixture specifications/type keys, materials, finishes, installation quantities and historical issue unresolved.
  • Complete branch/apparatus/circuit topology, architectural room registration and source-to-world coordinates unresolved.
  • Unvisited notes, schedules, margins, colored revisions and companion details require source-resolution review.
  • Extraction partial; modeling/checking unchecked; no architecture acceptance.
  • Complete branch endpoints and fixture identity require companion details and tracing.
  • Printed room identifiers and architectural-room registration unresolved.
  • Material, finish, fixture specification and installed quantity unresolved.
  • Remaining notes, riser sizes and revisions need source-resolution review; modeling/checking unchecked.
  • Governing sanitary fixture key/specification, manufacturer, fixture-body material and finish remain unestablished.
  • All unvisited notes, schedules, dimensions, callouts, revision marks and companion regions still require review.
  • Accepted architectural faces, source-to-building registration, fixture offsets, installed state and whole-building checks remain outstanding.
  • Complete unvisited notes, schedules, callouts, branches, margins and companion details need source-resolution review.
  • Governing historical revisions, installed quantities, architectural room registration and as-built correspondence remain unresolved.
  • Extraction remains partial; modeling/checking unchecked; no irrecoverable-gap conclusion.
  • Fixture type/specification, materials and finishes require a governing plumbing key or schedule.
  • Canonical architectural room registration, source-to-world position and installed state remain unresolved.
  • Complete branches, risers, annotations, revision authority and companion sheets remain partly unreviewed.

Download OCR observations (unverified)

Loading the selected drawing…

Scroll or pinch to inspect this drawing. Archival drawing photograph · Oregon Historical Society research collections.

Open source image separately ↗

32 matching properties

Printed values, calculations, image traces and observed counts are different kinds of evidence. “Verified” applies to the specific reading—not to the whole room or model.

parallel-img1346-detailverified · printed

drawing_title

FOURTH FLOOR PLAN

Partial service source evidence only; no installed count or accepted geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: FOURTH FLOOR PLAN

Partial service source evidence only; no installed count or accepted geometry.

parallel-img1346-detailverified · printed

floor_number

FOURTH FLOOR

4 floor

Partial service source evidence only; no installed count or accepted geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: FOURTH FLOOR

Partial service source evidence only; no installed count or accepted geometry.

parallel-img1346-detailverified · printed

discipline

PLUMBING

Partial service source evidence only; no installed count or accepted geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: PLUMBING

Partial service source evidence only; no installed count or accepted geometry.

parallel-img1346-detailverified · observed

service_layout

Plumbing routes and fixture symbols over architectural underlay

Partial service source evidence only; no installed count or accepted geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: Plumbing routes and fixture symbols over architectural underlay

Partial service source evidence only; no installed count or accepted geometry.

parallel-img1346-detailverified · observed

courtyard_underlay

Central court opening in floor underlay

Partial service source evidence only; no installed count or accepted geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: Central court opening in floor underlay

Partial service source evidence only; no installed count or accepted geometry.

parallel-img1346-detailunreviewed · printed

pipe_size

Fine pipe size callouts unresolved

Numeric value unresolved

Partial service source evidence only; no installed count or accepted geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: Fine pipe size callouts unresolved

Partial service source evidence only; no installed count or accepted geometry.

parallel-img1346-detailunreviewed · observed

fixture_count

Installed fixture count not established by locator

Numeric value unresolved

Partial service source evidence only; no installed count or accepted geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: Installed fixture count not established by locator

Partial service source evidence only; no installed count or accepted geometry.

parallel-img1346-detailunreviewed · observed

fixture_material

Fine fixture/material specification not reliably read

Partial service source evidence only; no installed count or accepted geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: Fine fixture/material specification not reliably read

Partial service source evidence only; no installed count or accepted geometry.

parallel-img1346-detailunreviewed · observed

room_assignments

Fine room numbers/use labels require targeted review

Partial service source evidence only; no installed count or accepted geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: Fine room numbers/use labels require targeted review

Partial service source evidence only; no installed count or accepted geometry.

parallel-img1346-detailverified · observed

original_linework

Original printed plumbing layout; no annotation substituted for original dimensions

Partial service source evidence only; no installed count or accepted geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: Original printed plumbing layout; no annotation substituted for original dimensions

Partial service source evidence only; no installed count or accepted geometry.

parallel-img1346-detailverified · observed

localized_fixture_groups

Grouped sanitary-fixture symbols near left raw core band

Partial service source evidence only; no installed count or accepted geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: Grouped sanitary-fixture symbols near left raw core band

Partial service source evidence only; no installed count or accepted geometry.

detail-plumbing-20261011b-1346verified · printed

core-waste-diameter

2" W

2 in

Source-local printed service callout or depicted fixture only; no whole-floor completeness, installed quantity or accepted architectural geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: 2" W

Source-local printed service callout or depicted fixture only; no whole-floor completeness, installed quantity or accepted architectural geometry.

detail-plumbing-20261011b-1346verified · printed

core-vent-diameter

2" V

2 in

Source-local printed service callout or depicted fixture only; no whole-floor completeness, installed quantity or accepted architectural geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: 2" V

Source-local printed service callout or depicted fixture only; no whole-floor completeness, installed quantity or accepted architectural geometry.

detail-plumbing-20261011b-1346verified · printed

core-hot-water-diameter

1/2" H.W.

0.5 in

Source-local printed service callout or depicted fixture only; no whole-floor completeness, installed quantity or accepted architectural geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: 1/2" H.W.

Source-local printed service callout or depicted fixture only; no whole-floor completeness, installed quantity or accepted architectural geometry.

detail-plumbing-20261011b-1346verified · printed

core-fixture-label

Drinking Fountain

Source-local printed service callout or depicted fixture only; no whole-floor completeness, installed quantity or accepted architectural geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: Drinking Fountain

Source-local printed service callout or depicted fixture only; no whole-floor completeness, installed quantity or accepted architectural geometry.

service-symbols-img1346-room442-branchverified · printed

rough_in_endpoint

Rough-in … to Wall line

Only legible instruction and endpoint clause are closed: rough-in terminates at wall line beside printedRoom442. Physical wall face and service-to-fixture mapping remain open.

IMG_1346 · Locate on drawing ↗

Drawing notation: Rough-in … to Wall line

Only legible instruction and endpoint clause are closed: rough-in terminates at wall line beside printedRoom442. Physical wall face and service-to-fixture mapping remain open.

service-symbols-img1346-room442-branchunreviewed · printed

rough_in_service_prefix

Rough-in H [separator unclear] C W to Wall line

Apparent H/CW service prefix retained as an insecure reading; no accepted connection or source geometry inferred.

IMG_1346 · Locate on drawing ↗

Drawing notation: Rough-in H [separator unclear] C W to Wall line

Apparent H/CW service prefix retained as an insecure reading; no accepted connection or source geometry inferred.

plumbingwitness1014i-img1346-room443-branchverified · printed

printed_room_number

443

443 identifier

Printed room witness only; accepted architectural registration unknown.

IMG_1346 · Locate on drawing ↗

Drawing notation: 443

Printed room witness only; accepted architectural registration unknown.

plumbingwitness1014i-img1346-room443-branchverified · printed

waste_nominal_diameter

2″ W

2 in

Room443 original local service bundle; nominal pipe size, no OD/elevation/fixture-spec interpretation.

IMG_1346 · Locate on drawing ↗

Drawing notation: 2″ W

Room443 original local service bundle; nominal pipe size, no OD/elevation/fixture-spec interpretation.

plumbingwitness1014i-img1346-room443-branchverified · printed

vent_nominal_diameter

2″ V

2 in

Room443 original local service bundle; nominal pipe size, no OD/elevation/fixture-spec interpretation.

IMG_1346 · Locate on drawing ↗

Drawing notation: 2″ V

Room443 original local service bundle; nominal pipe size, no OD/elevation/fixture-spec interpretation.

plumbingwitness1014i-img1346-room443-branchverified · printed

cold_water_nominal_diameter

1¼″ C.W.

1.25 in

Room443 original local service bundle; nominal pipe size, no OD/elevation/fixture-spec interpretation.

IMG_1346 · Locate on drawing ↗

Drawing notation: 1¼″ C.W.

Room443 original local service bundle; nominal pipe size, no OD/elevation/fixture-spec interpretation.

plumbingwitness1014i-img1346-room443-branchverified · printed

hot_water_nominal_diameter

¾″ H.W.

0.75 in

Room443 original local service bundle; nominal pipe size, no OD/elevation/fixture-spec interpretation.

IMG_1346 · Locate on drawing ↗

Drawing notation: ¾″ H.W.

Room443 original local service bundle; nominal pipe size, no OD/elevation/fixture-spec interpretation.

plumbingwitness1014i-img1346-room443-branchverified · printed

return_circulation_nominal_diameter

½″ R.C.

0.5 in

Room443 original local service bundle; nominal pipe size, no OD/elevation/fixture-spec interpretation.

IMG_1346 · Locate on drawing ↗

Drawing notation: ½″ R.C.

Room443 original local service bundle; nominal pipe size, no OD/elevation/fixture-spec interpretation.

service-symbols-img1346-room442-branchverified · printed

rough_in_service_note

Rough-in H & C W to Wall line

Local rough-in note specifies H & C W termination at wall line. Source wording preserved; does not assign fixture type, material, installed connection or accepted wall coordinates.

IMG_1346 · Locate on drawing ↗

Drawing notation: Rough-in H & C W to Wall line

Local rough-in note specifies H & C W termination at wall line. Source wording preserved; does not assign fixture type, material, installed connection or accepted wall coordinates.

Calculated from: plumbingnote1013e-img1346-001-rough_in_endpoint

service-symbols-img1346-room442-branchverified · printed

waste_nominal_diameter

2" W

2 in

Source-local printed property; diameter is nominal branch notation, not outside diameter, installation proof or exact room geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: 2" W

Source-local printed property; diameter is nominal branch notation, not outside diameter, installation proof or exact room geometry.

service-symbols-img1346-room442-branchverified · printed

vent_nominal_diameter

2" V

2 in

Source-local printed property; diameter is nominal branch notation, not outside diameter, installation proof or exact room geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: 2" V

Source-local printed property; diameter is nominal branch notation, not outside diameter, installation proof or exact room geometry.

service-symbols-img1346-room442-branchverified · printed

cold_water_nominal_diameter

1" C.W.

1 in

Source-local printed property; diameter is nominal branch notation, not outside diameter, installation proof or exact room geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: 1" C.W.

Source-local printed property; diameter is nominal branch notation, not outside diameter, installation proof or exact room geometry.

service-symbols-img1346-room442-branchverified · printed

hot_water_nominal_diameter

1" H.W.

1 in

Source-local printed property; diameter is nominal branch notation, not outside diameter, installation proof or exact room geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: 1" H.W.

Source-local printed property; diameter is nominal branch notation, not outside diameter, installation proof or exact room geometry.

service-symbols-img1346-room442-branchverified · printed

return_circulation_nominal_diameter

1/2" R.C.

0.5 in

Source-local printed property; diameter is nominal branch notation, not outside diameter, installation proof or exact room geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: 1/2" R.C.

Source-local printed property; diameter is nominal branch notation, not outside diameter, installation proof or exact room geometry.

service-symbols-img1346-room442-branchverified · printed

gas_nominal_diameter

3/4" Gas

0.75 in

Source-local printed property; diameter is nominal branch notation, not outside diameter, installation proof or exact room geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: 3/4" Gas

Source-local printed property; diameter is nominal branch notation, not outside diameter, installation proof or exact room geometry.

service-symbols-img1346-room442-branchverified · printed

printed_room_number_witness

442

442 identifier

Source-local printed property; diameter is nominal branch notation, not outside diameter, installation proof or exact room geometry.

IMG_1346 · Locate on drawing ↗

Drawing notation: 442

Source-local printed property; diameter is nominal branch notation, not outside diameter, installation proof or exact room geometry.

service-symbols-img1346-room442-branchillegible · printed

rough_in_note_unresolved

Rough-in / wall-pipe note above room442 branch; fine prefix and whole wording unresolved

Retain note as unreadable; no diameter or material supplied by guess.

IMG_1346 · Locate on drawing ↗

Drawing notation: Rough-in / wall-pipe note above room442 branch; fine prefix and whole wording unresolved

Retain note as unreadable; no diameter or material supplied by guess.