464 of 464 photographs have extraction records, containing 27,517 properties. Initial image review is not exhaustive extraction: 0 photographs have passed the full-region check. 66 numbered sheets are reconciled. Modeling and architectural registration are separate work; these counts do not establish a complete building.

Download the structured register (JSON)

Open the coordinated research model →

Clear filters
IMG_1339 · Folder 186

Plumbing Heating And Lighting

Original sheet identity has not yet been reconciled.

Extraction: Reviewed · extraction partial. Partial timed visual review: Text-first OCR/catalogue/report review, then one sequential <=1000px JPEG65 locator. Actual clockwise reading rotation 0 degrees. Raw normalized access-image coordinates before rotation. Partial only. Partial timed visual review: Text-first reuse of prior packages/OCR/queue only in this additive pass; no source image reopened. Partial timed visual review: Prior text evidence reused; source not reopened in this pass. Partial timed visual review: Prior OCR/report followed by targeted apparatus crop; partial fine evidence only. Partial timed visual review: Printed design evidence only; no installed count, room geometry or model acceptance. Partial timed visual review: Additive source-local lighting review; source regions normalized in unrotated access-image coordinates. Printed numbers are preserved separately from fixture types. No world coordinates, complete extraction or installed acceptance. Partial timed visual review: undefined Partial timed visual review: undefined Partial timed visual review: undefined Partial timed visual review: Additive partial source-local review; no accepted geometry or installed state. Partial timed visual review: Bounded source-local service evidence only; no physical coordinates, installed quantity or architectural release. Partial timed visual review: undefined Partial timed visual review: Bounded additive source review. Printed schedule quantities and source-local apparatus detail dimensions do not establish installed building geometry.

Unresolved extraction work
  • Partial 1000px JPEG65 locator only; all fine callouts, numeric dimensions and note regions require targeted follow-up
  • MEP underlay does not establish exact architectural room geometry
  • Register physical service instances, quantities, materials, pipe/circuit sizes and connections
  • Separate original printed linework from colored marks, signatures and revisions
  • Complete service-instance topology and room registration remain unresolved.
  • Governing fixture/material schedules and revision authority remain unresolved.
  • All unvisited regions require source-resolution review; modeling/checking unchecked.
  • Unvisited regions, schedules, annotations and companion details still require source-resolution review.
  • Installed service-instance topology, material schedules, room registration and governing revision remain unresolved.
  • Modeling and checking remain unchecked.
  • Final radiator schedule inlet/vent/stud cell blank; shared-value intent remains unresolved.
  • Individual service routes, pipe sizes, fixture identities and room registrations remain to be reviewed at source resolution.
  • Original/revised annotation authority and companion details unresolved.
  • No architectural outlines or model geometry inferred; modeling status unchecked.
  • Trace complete service connections and associate with architectural rooms.
  • Resolve materials, fixture specifications and governing revision.
  • Unvisited annotations and companion details remain pending; modeling and checking unchecked.
  • Printed symbol legend linking electrical outlet symbols to lighting specimen type marks
  • Fixture dimensions, materials and finishes
  • Accepted source-to-room/floor spatial registration and installed anchor height
  • As-built installation and revision authority
  • All unvisited notes, schedules, linework, callouts and companion details still require review
  • Drop-cord installation, counts, fixture type equivalence and exceptions unresolved.
  • Motor horsepower, apparatus capacity and other notes/routes remain open.
  • Governing revision and architectural registration remain unchecked.
  • Governing historical issue and as-built installation unresolved.
  • Architectural registration, installed quantities and physical geometry unchecked.
  • Unvisited notes, routes, schedules, callouts and companion details remain open; no whole-source completion or irrecoverable-gap claim.
  • Motor horsepower and apparatus capacity not reattempted without new evidence.
  • Governing original/revision authority and actual installation unresolved.
  • Architectural registration, room polygons, installed counts and physical routes unchecked.
  • Other regions, notes, schedules, callouts and companion details require review.
  • 25W drop-cord default reused as earlier text reading only, scoped UNLESS OTHERWISE NOTED; legacy candidate review retained, no newly verified wattage or whole-floor generalization.
  • Complete branch endpoints and fixture identity require companion details and tracing.
  • Printed room identifiers and architectural-room registration unresolved.
  • Material, finish, fixture specification and installed quantity unresolved.
  • Remaining notes, riser sizes and revisions need source-resolution review; modeling/checking unchecked.
  • Complete unvisited notes, schedules, callouts, branches, margins and companion details need source-resolution review.
  • Governing historical revisions, installed quantities, architectural room registration and as-built correspondence remain unresolved.
  • Extraction remains partial; modeling/checking unchecked; no irrecoverable-gap conclusion.
  • Historical revision authority and actual installation unresolved.
  • Architectural registration, installed counts and physical geometry unchecked.
  • Remaining regions, notes, schedules, routes and companion details require review.
  • Motor horsepower and apparatus capacities still unreadable; reference number does not close those numeric questions.
  • Full source-to-building registration, installed quantities and as-built correspondence remain unresolved.
  • Complete notes, schedules, callouts, margins and colored revision authority outside listed regions await review.
  • Extraction remains partial; modeling/checking unchecked. No irrecoverable evidence conclusion.

Download OCR observations (unverified)

Loading the selected drawing…

Scroll or pinch to inspect this drawing. Archival drawing photograph · Oregon Historical Society research collections.

Open source image separately ↗

33 matching properties

Printed values, calculations, image traces and observed counts are different kinds of evidence. “Verified” applies to the specific reading—not to the whole room or model.

parallel-img1339-detailverified · printed

plan_title

EIGHTH FLOOR AND ATTIC PLUMBING HEATING AND LIGHTING

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: EIGHTH FLOOR AND ATTIC PLUMBING HEATING AND LIGHTING

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

parallel-img1339-detailverified · printed

service_discipline

PLUMBING HEATING AND LIGHTING

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: PLUMBING HEATING AND LIGHTING

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

parallel-img1339-detailverified · printed

floor_number

EIGHTH FLOOR

8 floor

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: EIGHTH FLOOR

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

parallel-img1339-detailverified · observed

service_plan_extent

Piping/circuit layout over architectural underlay

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: Piping/circuit layout over architectural underlay

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

parallel-img1339-detailunreviewed · printed

pipe_or_circuit_size

Fine printed sizes unresolved at locator scale

Numeric value unresolved

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: Fine printed sizes unresolved at locator scale

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

parallel-img1339-detailunreviewed · observed

architectural_clear_dimensions

Architectural underlay dimensions not reliably extracted

Numeric value unresolved

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: Architectural underlay dimensions not reliably extracted

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

parallel-img1339-detailverified · observed

original_annotation_separation

Printed service linework retained; signatures/colored marks not treated as revised measurements

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: Printed service linework retained; signatures/colored marks not treated as revised measurements

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

parallel-img1339-detailverified · printed

attic_assignment

EIGHTH FLOOR & ATTIC PLAN

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: EIGHTH FLOOR & ATTIC PLAN

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

parallel-img1339-detailunreviewed · observed

tank_detail_callouts

Dense localized apparatus/piping region lower right remains unresolved

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: Dense localized apparatus/piping region lower right remains unresolved

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

parallel-img1339-detailunreviewed · observed

right_note

Right note block remains unresolved

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: Right note block remains unresolved

Partial service drawing/detail evidence; no installed count or accepted architectural geometry.

detail-mech1339b-apparatusverified · printed

panel_mark

PANEL P2

Partial localized apparatus review only; room underlay does not establish geometry.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: PANEL P2

Partial localized apparatus review only; room underlay does not establish geometry.

detail-mech1339b-apparatusverified · printed

panel_mark

PANEL P6

Partial localized apparatus review only; room underlay does not establish geometry.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: PANEL P6

Partial localized apparatus review only; room underlay does not establish geometry.

detail-mech1339b-apparatusverified · printed

local_assignment

STAIR D

Partial localized apparatus review only; room underlay does not establish geometry.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: STAIR D

Partial localized apparatus review only; room underlay does not establish geometry.

detail-mech1339b-apparatusunreviewed · printed

companion_reference

SEE DRAWING NO PH 472 FOR UPPER PART OF FAN ROOM / SEE DRAWING NO PH 460 FOR SECTION C-C

Partial localized apparatus review only; room underlay does not establish geometry.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: SEE DRAWING NO PH 472 FOR UPPER PART OF FAN ROOM / SEE DRAWING NO PH 460 FOR SECTION C-C

Partial localized apparatus review only; room underlay does not establish geometry.

detail-mech1339b-apparatusunreviewed · observed

apparatus_labels

Apparatus and motor labels partly legible; exact equipment types and material unresolved

Partial localized apparatus review only; room underlay does not establish geometry.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: Apparatus and motor labels partly legible; exact equipment types and material unresolved

Partial localized apparatus review only; room underlay does not establish geometry.

detail-plumbing-20261012c-1339-heating-noteverified · printed

radiator-tube-count

ALL RADIATORS ON THIS FLOOR TO BE 3 TUBE … HIGH UNLESS OTHERWISE NOTED

3 count

Printed design evidence only; no installed count, room geometry or model acceptance.

IMG_1339 · WPHL-459 · Locate on drawing ↗

Drawing notation: ALL RADIATORS ON THIS FLOOR TO BE 3 TUBE … HIGH UNLESS OTHERWISE NOTED

Printed design evidence only; no installed count, room geometry or model acceptance.

detail-plumbing-20261012c-1339-heating-noteunresolved · printed

radiator-height

… HIGH UNLESS OTHERWISE NOTED

Numeric value unresolved

Printed design evidence only; no installed count, room geometry or model acceptance.

IMG_1339 · WPHL-459 · Locate on drawing ↗

Drawing notation: … HIGH UNLESS OTHERWISE NOTED

Printed design evidence only; no installed count, room geometry or model acceptance.

detail-plumbing-20261012c-1339-heating-noteverified · printed

connection-routing

ALL HEATING CONNECTIONS SHALL BE BROUGHT THRU FLOOR

Printed design evidence only; no installed count, room geometry or model acceptance.

IMG_1339 · WPHL-459 · Locate on drawing ↗

Drawing notation: ALL HEATING CONNECTIONS SHALL BE BROUGHT THRU FLOOR

Printed design evidence only; no installed count, room geometry or model acceptance.

detail-plumbing-20261012c-1339-heating-noteverified · printed

drop-riser-valving

VALVE ALL STEAM DROP RISERS AT TOP AND BOTTOM

Printed design evidence only; no installed count, room geometry or model acceptance.

IMG_1339 · WPHL-459 · Locate on drawing ↗

Drawing notation: VALVE ALL STEAM DROP RISERS AT TOP AND BOTTOM

Printed design evidence only; no installed count, room geometry or model acceptance.

lighting-img1339-20261013a-drop-cord-noteunreviewed · printed

drop_cord_outlet_power_default

ELECTRICAL SYSTEM / All Drop Cord Outlets to Be25 Watt Unless Otherwise Noted

25 W

Reading from whole2200px access derivative only; targeted source crop still required to verify exact wording/glyphs. Applies to drop-cord outlet rule, not installed quantities or pendant specimen types.

IMG_1339 · WHL-459 · Locate on drawing ↗

Drawing notation: ELECTRICAL SYSTEM / All Drop Cord Outlets to Be25 Watt Unless Otherwise Noted

Reading from whole2200px access derivative only; targeted source crop still required to verify exact wording/glyphs. Applies to drop-cord outlet rule, not installed quantities or pendant specimen types.

lighting-img1339-20261013a-drop-cord-noteverified · printed

drop_cord_outlet_power_default

ELECTRICAL SYSTEM / All Drop Cord Outlets To Be 25 Watt Unless Otherwise Noted

25 W

Exact source default for drop-cord outlets, qualified Unless Otherwise Noted. Same target and value/unit as historical unreviewed candidate. Does not establish installed number, P-type equivalent or the rating of every circular symbol.

IMG_1339 · Locate on drawing ↗

Drawing notation: ELECTRICAL SYSTEM / All Drop Cord Outlets To Be 25 Watt Unless Otherwise Noted

Exact source default for drop-cord outlets, qualified Unless Otherwise Noted. Same target and value/unit as historical unreviewed candidate. Does not establish installed number, P-type equivalent or the rating of every circular symbol.

mepwitness1014h-1339-left-fan-no1verified · printed

fan_designation

FAN NO.1

Local printed fan designation in apparatus field only. Number is a source apparatus designation, not a count of installed fans or a motor rating.

IMG_1339 · Locate on drawing ↗

Drawing notation: FAN NO.1

Local printed fan designation in apparatus field only. Number is a source apparatus designation, not a count of installed fans or a motor rating.

mepwitness1014h-1339-right-fan-no2verified · printed

fan_designation

FAN NO.2

Local printed fan designation in apparatus field only. Number is a source apparatus designation, not a count of installed fans or a motor rating.

IMG_1339 · Locate on drawing ↗

Drawing notation: FAN NO.2

Local printed fan designation in apparatus field only. Number is a source apparatus designation, not a count of installed fans or a motor rating.

detail-mech1339b-apparatusverified · printed

upper_fan_room_companion_number

SEE DRAWING NO. PHL470 FOR UPPER PART OF FAN ROOM

470 sheet-number

Same original upper-fan-room row, visible prefixPHL and470. No companion installation identity or revision authority.

IMG_1339 · Locate on drawing ↗

Drawing notation: SEE DRAWING NO. PHL470 FOR UPPER PART OF FAN ROOM

Same original upper-fan-room row, visible prefixPHL and470. No companion installation identity or revision authority.

Conflicting readings: detail-mech1339b-note

detail-mech1339b-apparatusverified · printed

upper_fan_room_companion_designation

SEE DRAWING NO. PHL470 FOR UPPER PART OF FAN ROOM

FullPHL470 token preserved; older provisional472 remains historical.

IMG_1339 · Locate on drawing ↗

Drawing notation: SEE DRAWING NO. PHL470 FOR UPPER PART OF FAN ROOM

FullPHL470 token preserved; older provisional472 remains historical.

detail-mech1339b-apparatusverified · printed

flexible_connection_material

CANVAS CONNECTION

Printed material annotation for local apparatus connection. No canvas thickness, finish or installed number established.

IMG_1339 · Locate on drawing ↗

Drawing notation: CANVAS CONNECTION

Printed material annotation for local apparatus connection. No canvas thickness, finish or installed number established.

detail-mech1339b-apparatusverified · printed

air_filter_label

FILTER

Source-local printed schedule/detail property only; no installed quantity, physical coordinates or architectural approval.

IMG_1339 · Locate on drawing ↗

Drawing notation: FILTER

Source-local printed schedule/detail property only; no installed quantity, physical coordinates or architectural approval.

detail-mech1339b-apparatusverified · printed

apparatus_drain_destination

DRAIN TO SOIL COLUMN

Source-local printed schedule/detail property only; no installed quantity, physical coordinates or architectural approval.

IMG_1339 · Locate on drawing ↗

Drawing notation: DRAIN TO SOIL COLUMN

Source-local printed schedule/detail property only; no installed quantity, physical coordinates or architectural approval.

detail-mech1339b-apparatusverified · printed

return_route_relation

RETURN UNDER FLOOR

Source-local printed schedule/detail property only; no installed quantity, physical coordinates or architectural approval.

IMG_1339 · Locate on drawing ↗

Drawing notation: RETURN UNDER FLOOR

Source-local printed schedule/detail property only; no installed quantity, physical coordinates or architectural approval.

detail-mech1339b-apparatusunreviewed · printed

upper_fan_room_companion_number

SEE DRAWING NO. PH[L?]470 FOR UPPER PART OF FAN ROOM

Numeric value unresolved

Candidate470 visible in new apparatus crop; prefix and complete numeral need a closer separate crop. Earlier provisional472 remains preserved without withdrawal.

IMG_1339 · Locate on drawing ↗

Drawing notation: SEE DRAWING NO. PH[L?]470 FOR UPPER PART OF FAN ROOM

Candidate470 visible in new apparatus crop; prefix and complete numeral need a closer separate crop. Earlier provisional472 remains preserved without withdrawal.

Conflicting readings: detail-mech1339b-note

detail-mech1339b-apparatusverified · printed

section_cc_companion_number

SEE DRAWING NO. PH460 FOR SECTION C-C

460 sheet-number

Printed section C-C reference only; no physical identity merge with companion.

IMG_1339 · Locate on drawing ↗

Drawing notation: SEE DRAWING NO. PH460 FOR SECTION C-C

Printed section C-C reference only; no physical identity merge with companion.

detail-mech1339b-apparatusunreviewed · observed

apparatus_capacity_unreadable

Fan/motor fine ratings not confidently readable in current native crop

Numeric value unresolved

Source-local printed schedule/detail property only; no installed quantity, physical coordinates or architectural approval.

IMG_1339 · Locate on drawing ↗

Drawing notation: Fan/motor fine ratings not confidently readable in current native crop

Source-local printed schedule/detail property only; no installed quantity, physical coordinates or architectural approval.

detail-plumbing-20261012c-1339-heating-noteverified · printed

radiator_height

ALL RADIATORS ON THIS FLOOR TO BE 3 TUBE / 26″ HIGH UNLESS OTHERWISE NOTED

26 in

Printed default radiator height scoped to this eighth-floor/attic drawing and qualified UNLESS OTHERWISE NOTED. Reuses3-tube specification; no installed radiator count or floor geometry.

IMG_1339 · Locate on drawing ↗

Drawing notation: ALL RADIATORS ON THIS FLOOR TO BE 3 TUBE / 26″ HIGH UNLESS OTHERWISE NOTED

Printed default radiator height scoped to this eighth-floor/attic drawing and qualified UNLESS OTHERWISE NOTED. Reuses3-tube specification; no installed radiator count or floor geometry.