Printed values, calculations, image traces and observed counts are different kinds of evidence. “Verified” applies to the specific reading—not to the whole room or model.
detail-mech1338b-breaker-lighting-3verified · printed
switchboard
MAIN SWITCHBOARD LIGHTINGPrinted schedule property only. Stable extraction instance represents a schedule row; installed location/floor and physical equipment identity unresolved. Yellow handwriting is not substituted for original printed rating.
IMG_1338 · Locate on drawing ↗Drawing notation: MAIN SWITCHBOARD LIGHTING
Printed schedule property only. Stable extraction instance represents a schedule row; installed location/floor and physical equipment identity unresolved. Yellow handwriting is not substituted for original printed rating.
detail-mech1338b-breaker-lighting-3verified · printed
circuit_assignment
Feeder BPrinted schedule property only. Stable extraction instance represents a schedule row; installed location/floor and physical equipment identity unresolved. Yellow handwriting is not substituted for original printed rating.
IMG_1338 · Locate on drawing ↗Drawing notation: Feeder B
Printed schedule property only. Stable extraction instance represents a schedule row; installed location/floor and physical equipment identity unresolved. Yellow handwriting is not substituted for original printed rating.
detail-mech1338b-breaker-lighting-3verified · printed
quantity
11 count
Printed schedule property only. Stable extraction instance represents a schedule row; installed location/floor and physical equipment identity unresolved. Yellow handwriting is not substituted for original printed rating.
IMG_1338 · Locate on drawing ↗Drawing notation: 1
Printed schedule property only. Stable extraction instance represents a schedule row; installed location/floor and physical equipment identity unresolved. Yellow handwriting is not substituted for original printed rating.
detail-mech1338b-breaker-lighting-3unreviewed · printed
rating_amperes
240240 A
Printed schedule property only. Stable extraction instance represents a schedule row; installed location/floor and physical equipment identity unresolved. Yellow handwriting is not substituted for original printed rating. Review correction review-correction-20261013f-feeder-rating: The native IMG1338 schedule re-read resolves the same original printed amperes cell as200A, not240A. No yellow handwritten revision or different row explains the discrepancy. The older240A remains an extraction audit record, not an installed equipment rating.
IMG_1338 · Locate on drawing ↗Drawing notation: 240
Printed schedule property only. Stable extraction instance represents a schedule row; installed location/floor and physical equipment identity unresolved. Yellow handwriting is not substituted for original printed rating.
detail-mech1338b-breaker-lighting-3verified · printed
poles
33 count
Printed schedule property only. Stable extraction instance represents a schedule row; installed location/floor and physical equipment identity unresolved. Yellow handwriting is not substituted for original printed rating.
IMG_1338 · Locate on drawing ↗Drawing notation: 3
Printed schedule property only. Stable extraction instance represents a schedule row; installed location/floor and physical equipment identity unresolved. Yellow handwriting is not substituted for original printed rating.
detail-mech1338b-breaker-lighting-3verified · printed
rating_amperes
200200 A
Verified same-image re-read of original white printed schedule cell; not yellow handwriting and not a historical revision. Preserve older reading pending explicit primary correction; schedule row remains distinct from installed equipment.
IMG_1338 · Locate on drawing ↗Drawing notation: 200
Verified same-image re-read of original white printed schedule cell; not yellow handwriting and not a historical revision. Preserve older reading pending explicit primary correction; schedule row remains distinct from installed equipment.
Conflicting readings: detail-mech1338b-m014