Gus J. SolomonUnited States Courthouse
← Back to the building1933 reconstruction · research preview

The measured building.

Every dimension belongs to an object and a drawing. Original room numbers, object marks, printed values and source regions stay together—even when the answer is unresolved.

Source photographs
464
Identified objects
4872
Verified printed values
12046
Disputed values
20

464 of 464 photographs have extraction records, containing 27,517 properties. Initial image review is not exhaustive extraction: 0 photographs have passed the full-region check. 66 numbered sheets are reconciled. Modeling and architectural registration are separate work; these counts do not establish a complete building.

Download the structured register (JSON)

Open the coordinated research model →

Clear filters

1 matching properties

Printed values, calculations, image traces and observed counts are different kinds of evidence. “Verified” applies to the specific reading—not to the whole room or model.

f1-public-lobby-w217-bay-p-elevator-no2-entranceverified · derived

Elevator No. 2 analytical finished-entrance envelope placement

Accepted · zero-thickness evidence review only

W217 supplies an exact symmetric 24'-11" Bay P plan, a 6-foot central paired door, and a separately chained 3'-6" Elevator No. 2 finished entrance. Centering that exact plan on the independently labeled W3 Bay P wall leaves 1.256-foot endpoint residuals and a 1.468-foot held-out door-center residual, both within W3's recorded 2-foot trace uncertainty. The W3 door trace is only 3.9 feet wide and its south endpoint fails the 2-foot check, so it is treated as an incomplete swing-arc trace and is not used to resize the verified W217 leaves. A separate old W3 line classified as the Elevator No. 2 threshold is 6.957 feet from the W217-predicted entrance center and differs in orientation by 89.695 degrees; targeted review confirms it is not the Bay P-parallel entrance plane, so that provisional trace is disputed and excluded. The checked registration places the zero-thickness analytical door leaves and Elevator No. 2 finished-entrance envelope only; it does not establish physical wall, frame, shaft, cab, or equipment geometry.

IMG_1095 · sheet-W217 · Locate on drawing ↗

Drawing notation: PLAN OF BAY P; ELEVATOR No. 2

Full-sheet text and existing reports were read first; the complete sheet and sequential Bay P plan crops were then inspected one image at a time.

IMG_1202 · sheet-W3 · Locate on drawing ↗

Drawing notation: BAY P; ELEVATOR NO. 2

The W3 registration is provisional. Bay P wall endpoints and the double-door segment are traced plan controls with a conservative 2-foot uncertainty, not surveyed construction faces.

Source-by-source coverage

Source inventory is separate from the floor filters above. Select one drawing to inspect it; no drawing set is preloaded.