464 of 464 photographs have extraction records, containing 27,517 properties. Initial image review is not exhaustive extraction: 0 photographs have passed the full-region check. 66 numbered sheets are reconciled. Modeling and architectural registration are separate work; these counts do not establish a complete building.

Download the structured register (JSON)

Open the coordinated research model →

Clear filters
IMG_1332 · Folder 186

Heating And Lighting

Original sheet identity has not yet been reconciled.

Extraction: Reviewed · extraction partial. Partial timed visual review: Partial catalogue/OCR-first then sequential <=1000px JPEG65 locator review of public/archive/drawings/complete-upright/IMG_1332.webp. IMG_1322 additionally has one 250x435 post-schedule crop. Regions normalized in unrotated access-image coordinates; rotationDegrees is clockwise correction. Selected evidence only, no full extraction/modeling. Partial timed visual review: 2026-10-11 remaining-region review. Prior queue, OCR and packages reused; ten sequential inspections total, confined to IMG_1329/1334/1336/1337. Normalized regions in unrotated complete-upright WebP. Research only; no accepted geometry or complete extraction. Partial timed visual review: OCR and prior package text review only this pass; no new visual verification. Partial timed visual review: Additive source-local review; normalized coordinates in unrotated 2200×1650 access WebP. Reuse previous verified records; no accepted geometry or complete extraction. Partial timed visual review: Additive source-local lighting review; source regions normalized in unrotated access-image coordinates. Printed numbers are preserved separately from fixture types. No world coordinates, complete extraction or installed acceptance. Partial timed visual review: undefined Partial timed visual review: New readings use raw 4032x3024 master-image coordinates, ignoring EXIF. Regional identities are modern extraction IDs, not historical identifiers. No accepted installed transforms or building geometry. Partial timed visual review: undefined Partial timed visual review: undefined

Unresolved extraction work
  • partial locator coverage; remaining individual beam/member sizes, schedules, fine fractions and dimensions outstanding
  • all notes, revisions, symbols, utility legends and companion details require reconciliation
  • historical instance locations, material grades, connection capacities and modeling checks missing
  • Remaining individual dimensions, service/member instances, schedules, material and connection details require source review.
  • Original/revised annotation authority and companion registrations remain unresolved.
  • Architectural geometry and installed quantities are not established by service underlays.
  • Individual service routes, pipe sizes, fixture identities and room registrations remain to be reviewed at source resolution.
  • Original/revised annotation authority and companion details unresolved.
  • No architectural outlines or model geometry inferred; modeling status unchecked.
  • Remaining individual dimensions, service instances, fine callouts and routes require source review.
  • Original/revised annotations, companion sheets and installed registration unresolved.
  • Architectural geometry and installed quantities are not established; model unchecked.
  • Printed symbol legend linking electrical outlet symbols to lighting specimen type marks
  • Fixture dimensions, materials and finishes
  • Accepted source-to-room/floor spatial registration and installed anchor height
  • As-built installation and revision authority
  • All unvisited notes, schedules, linework, callouts and companion details still require review
  • PUBLIC LOBBY station750 annotation correlation with P-5 fixture specimen
  • All other first-floor outlet stations and distinct symbol families
  • Resolve installed meaning of drawn station locations through governing revision and accepted registration
  • Fixture type-symbol key and installed counts remain unresolved.
  • Complete notes, schedules, routes, revision authority and registration remain open.
  • Governing luminaire symbol/P-type key and type-to-instance mapping
  • Fixture material, finish and dimensional envelope
  • Mounting/anchor height, station spacing and checked architectural-room/source transform
  • Governing revision, installed quantity and as-built correspondence
  • Other sheet regions, notes, exceptions and companion details remain unreviewed
  • Mailing Vestibule and Registry visible in crop retain unenumerated station rows; existing four public-lobby750 stations reused rather than duplicated.
  • Existing ceiling300W/bracket50W defaults and Work Space receptacle height do not establish200/750-mark meanings or a P-type key.
  • Governing original/revision authority and actual installation unresolved.
  • Architectural registration, room polygons, installed counts and physical routes unchecked.
  • Other regions, notes, schedules, callouts and companion details require review.
  • Prior station glyphs/circuit labels do not establish a P-type fixture equivalence. No new image inspection or source-key mapping in this pass.
  • Governing historical issue, annotation authority and actual installation remain unresolved.
  • Individual radiator/boot/pipe/trap instances, exceptions, dimensions and physical registration remain unchecked.
  • Remaining sheet regions, schedules, route sizes and companion details require review; no full-source completion or modeling approval.

Download OCR observations (unverified)

Loading the selected drawing…

Scroll or pinch to inspect this drawing. Archival drawing photograph · Oregon Historical Society research collections.

Open source image separately ↗

43 matching properties

Printed values, calculations, image traces and observed counts are different kinds of evidence. “Verified” applies to the specific reading—not to the whole room or model.

parallel-img1332-servicesverified · printed

system_assignment

HEATING AND LIGHTING

Selected visible source evidence only; partial review, applies to depicted assembly.

IMG_1332 · Locate on drawing ↗

Drawing notation: HEATING AND LIGHTING

Selected visible source evidence only; partial review, applies to depicted assembly.

parallel-img1332-servicesverified · printed

floor_assignment

FIRST FLOOR PLAN

Selected visible source evidence only; partial review, applies to depicted assembly.

IMG_1332 · Locate on drawing ↗

Drawing notation: FIRST FLOOR PLAN

Selected visible source evidence only; partial review, applies to depicted assembly.

parallel-img1332-servicesverified · observed

system_routes

Dense branching linework, circular fixture symbols and perimeter equipment shown

Selected visible source evidence only; partial review, applies to depicted assembly.

IMG_1332 · Locate on drawing ↗

Drawing notation: Dense branching linework, circular fixture symbols and perimeter equipment shown

Selected visible source evidence only; partial review, applies to depicted assembly.

parallel-img1332-servicesunreviewed · printed

fixture_quantities

Unresolved

Numeric value unresolved

Selected visible source evidence only; partial review, applies to depicted assembly.

IMG_1332 · Locate on drawing ↗

Selected visible source evidence only; partial review, applies to depicted assembly.

parallel-img1332-servicesunreviewed · printed

pipe_sizes

Unresolved

Numeric value unresolved

Selected visible source evidence only; partial review, applies to depicted assembly.

IMG_1332 · Locate on drawing ↗

Selected visible source evidence only; partial review, applies to depicted assembly.

parallel-img1332-servicesunreviewed · printed

fixture_type_schedule

Unresolved

Selected visible source evidence only; partial review, applies to depicted assembly.

IMG_1332 · Locate on drawing ↗

Selected visible source evidence only; partial review, applies to depicted assembly.

parallel-img1332-servicesunreviewed · printed

electrical_circuit_identity

Unresolved

Selected visible source evidence only; partial review, applies to depicted assembly.

IMG_1332 · Locate on drawing ↗

Selected visible source evidence only; partial review, applies to depicted assembly.

parallel-img1332-servicesunreviewed · observed

colored_annotation

Red colored route/mark annotations present

Separate visible annotation; revision authority and exact circuit values unresolved.

IMG_1332 · Locate on drawing ↗

Drawing notation: Red colored route/mark annotations present

Separate visible annotation; revision authority and exact circuit values unresolved.

lighting-img1332-20261013a-public-lobby-outlet-runverified · printed

room_assignment

PUBLIC LOBBY

Source-local property only; no accepted installed transform or fixture type association.

IMG_1332 · Locate on drawing ↗

Drawing notation: PUBLIC LOBBY

Source-local property only; no accepted installed transform or fixture type association.

lighting-img1332-20261013a-public-lobby-outlet-runverified · observed

observed_outlet_station_count

Four circular electrical outlet symbols on horizontal PUBLIC LOBBY run

4 count

Count of drawn outlet stations in the marked lobby run. Does not identify fixture P-5, number of lamps per fixture, or accepted installed centers.

IMG_1332 · Locate on drawing ↗

Drawing notation: Four circular electrical outlet symbols on horizontal PUBLIC LOBBY run

Count of drawn outlet stations in the marked lobby run. Does not identify fixture P-5, number of lamps per fixture, or accepted installed centers.

lighting-img1332-20261013a-public-lobby-station-1verified · observed

drawn_outlet_station_count

One circular electrical outlet station

1 count

Source-local property only; no accepted installed transform or fixture type association.

IMG_1332 · Locate on drawing ↗

Drawing notation: One circular electrical outlet station

Source-local property only; no accepted installed transform or fixture type association.

lighting-img1332-20261013a-public-lobby-station-1verified · printed

printed_station_number

750

750 number

Source-local property only; no accepted installed transform or fixture type association.

IMG_1332 · Locate on drawing ↗

Drawing notation: 750

Source-local property only; no accepted installed transform or fixture type association.

lighting-img1332-20261013a-public-lobby-station-1unreviewed · inferred

candidate_outlet_power

750 [W inferred from electrical-system note context]

750 W

Power interpretation of station annotation only; note elsewhere uses W for outlet ratings. No lighting specimen identity or whole-fixture consumption accepted.

IMG_1332 · Locate on drawing ↗

Drawing notation: 750 [W inferred from electrical-system note context]

Power interpretation of station annotation only; note elsewhere uses W for outlet ratings. No lighting specimen identity or whole-fixture consumption accepted.

Calculated from: lighting1013a-img1332-printed_station_number-4

lighting-img1332-20261013a-public-lobby-station-1unreviewed · printed

fixture_type_identity

Unresolved

Source-local property only; no accepted installed transform or fixture type association.

IMG_1332 · Locate on drawing ↗

Source-local property only; no accepted installed transform or fixture type association.

lighting-img1332-20261013a-public-lobby-station-2verified · observed

drawn_outlet_station_count

One circular electrical outlet station

1 count

Source-local property only; no accepted installed transform or fixture type association.

IMG_1332 · Locate on drawing ↗

Drawing notation: One circular electrical outlet station

Source-local property only; no accepted installed transform or fixture type association.

lighting-img1332-20261013a-public-lobby-station-2verified · printed

printed_station_number

750

750 number

Source-local property only; no accepted installed transform or fixture type association.

IMG_1332 · Locate on drawing ↗

Drawing notation: 750

Source-local property only; no accepted installed transform or fixture type association.

lighting-img1332-20261013a-public-lobby-station-2unreviewed · inferred

candidate_outlet_power

750 [W inferred from electrical-system note context]

750 W

Power interpretation of station annotation only; note elsewhere uses W for outlet ratings. No lighting specimen identity or whole-fixture consumption accepted.

IMG_1332 · Locate on drawing ↗

Drawing notation: 750 [W inferred from electrical-system note context]

Power interpretation of station annotation only; note elsewhere uses W for outlet ratings. No lighting specimen identity or whole-fixture consumption accepted.

Calculated from: lighting1013a-img1332-printed_station_number-8

lighting-img1332-20261013a-public-lobby-station-2unreviewed · printed

fixture_type_identity

Unresolved

Source-local property only; no accepted installed transform or fixture type association.

IMG_1332 · Locate on drawing ↗

Source-local property only; no accepted installed transform or fixture type association.

lighting-img1332-20261013a-public-lobby-station-3verified · observed

drawn_outlet_station_count

One circular electrical outlet station

1 count

Source-local property only; no accepted installed transform or fixture type association.

IMG_1332 · Locate on drawing ↗

Drawing notation: One circular electrical outlet station

Source-local property only; no accepted installed transform or fixture type association.

lighting-img1332-20261013a-public-lobby-station-3verified · printed

printed_station_number

750

750 number

Source-local property only; no accepted installed transform or fixture type association.

IMG_1332 · Locate on drawing ↗

Drawing notation: 750

Source-local property only; no accepted installed transform or fixture type association.

lighting-img1332-20261013a-public-lobby-station-3unreviewed · inferred

candidate_outlet_power

750 [W inferred from electrical-system note context]

750 W

Power interpretation of station annotation only; note elsewhere uses W for outlet ratings. No lighting specimen identity or whole-fixture consumption accepted.

IMG_1332 · Locate on drawing ↗

Drawing notation: 750 [W inferred from electrical-system note context]

Power interpretation of station annotation only; note elsewhere uses W for outlet ratings. No lighting specimen identity or whole-fixture consumption accepted.

Calculated from: lighting1013a-img1332-printed_station_number-12

lighting-img1332-20261013a-public-lobby-station-3unreviewed · printed

fixture_type_identity

Unresolved

Source-local property only; no accepted installed transform or fixture type association.

IMG_1332 · Locate on drawing ↗

Source-local property only; no accepted installed transform or fixture type association.

lighting-img1332-20261013a-public-lobby-station-4verified · observed

drawn_outlet_station_count

One circular electrical outlet station

1 count

Source-local property only; no accepted installed transform or fixture type association.

IMG_1332 · Locate on drawing ↗

Drawing notation: One circular electrical outlet station

Source-local property only; no accepted installed transform or fixture type association.

lighting-img1332-20261013a-public-lobby-station-4verified · printed

printed_station_number

750

750 number

Source-local property only; no accepted installed transform or fixture type association.

IMG_1332 · Locate on drawing ↗

Drawing notation: 750

Source-local property only; no accepted installed transform or fixture type association.

lighting-img1332-20261013a-public-lobby-station-4unreviewed · inferred

candidate_outlet_power

750 [W inferred from electrical-system note context]

750 W

Power interpretation of station annotation only; note elsewhere uses W for outlet ratings. No lighting specimen identity or whole-fixture consumption accepted.

IMG_1332 · Locate on drawing ↗

Drawing notation: 750 [W inferred from electrical-system note context]

Power interpretation of station annotation only; note elsewhere uses W for outlet ratings. No lighting specimen identity or whole-fixture consumption accepted.

Calculated from: lighting1013a-img1332-printed_station_number-16

lighting-img1332-20261013a-public-lobby-station-4unreviewed · printed

fixture_type_identity

Unresolved

Source-local property only; no accepted installed transform or fixture type association.

IMG_1332 · Locate on drawing ↗

Source-local property only; no accepted installed transform or fixture type association.

lighting-img1332-20261013a-electrical-noteverified · printed

ceiling_outlet_default_power

All ceiling outlets to be 300 W. Unless otherwise noted.

300 W

Printed ceiling-outlet default with explicit exception; not an installed count or lamp/type schedule.

IMG_1332 · Locate on drawing ↗

Drawing notation: All ceiling outlets to be 300 W. Unless otherwise noted.

Printed ceiling-outlet default with explicit exception; not an installed count or lamp/type schedule.

lighting-img1332-20261013a-electrical-noteverified · printed

bracket_outlet_default_power

All bracket outlets to be 50 W. unless otherwise noted.

50 W

Printed bracket-outlet default with explicit exception; distinct from ceiling outlets and lobby750 station labels.

IMG_1332 · Locate on drawing ↗

Drawing notation: All bracket outlets to be 50 W. unless otherwise noted.

Printed bracket-outlet default with explicit exception; distinct from ceiling outlets and lobby750 station labels.

lighting-img1332-20261013a-electrical-noteverified · printed

wall_receptacle_height

All wall receptacles to be located 5′-0″ above floor in Work Space

60 in

Printed wall-receptacle height rule applies to Work Space. Not a pendant drop or fixture center elevation.

IMG_1332 · Locate on drawing ↗

Drawing notation: All wall receptacles to be located 5′-0″ above floor in Work Space

Printed wall-receptacle height rule applies to Work Space. Not a pendant drop or fixture center elevation.

lighting1013d-img1332-cod-delivery-row-station-01verified · observed

drawn_outlet_station_presence

One plain circular electrical outlet symbol

1 count

Source-local drawn evidence only; not accepted installed geometry, quantity, lamp wattage or P-type mapping.

IMG_1332 · Locate on drawing ↗

Drawing notation: One plain circular electrical outlet symbol

Source-local drawn evidence only; not accepted installed geometry, quantity, lamp wattage or P-type mapping.

lighting1013d-img1332-cod-delivery-row-station-01verified · printed

printed_station_number

200

200 number

Printed number beside station; no local W suffix or governing P-type correlation certified. Number is neither historical instance ID nor installed quantity.

IMG_1332 · Locate on drawing ↗

Drawing notation: 200

Printed number beside station; no local W suffix or governing P-type correlation certified. Number is neither historical instance ID nor installed quantity.

lighting1013d-img1332-cod-delivery-row-station-01unreviewed · observed

luminaire_type_mapping

Unresolved

No governing fixture/P-type key verified in this bounded station crop; not evidence that no key survives elsewhere.

IMG_1332 · Locate on drawing ↗

No governing fixture/P-type key verified in this bounded station crop; not evidence that no key survives elsewhere.

lighting1013d-img1332-cod-delivery-row-station-02verified · observed

drawn_outlet_station_presence

One plain circular electrical outlet symbol

1 count

Source-local drawn evidence only; not accepted installed geometry, quantity, lamp wattage or P-type mapping.

IMG_1332 · Locate on drawing ↗

Drawing notation: One plain circular electrical outlet symbol

Source-local drawn evidence only; not accepted installed geometry, quantity, lamp wattage or P-type mapping.

lighting1013d-img1332-cod-delivery-row-station-02verified · printed

printed_station_number

200

200 number

Printed number beside station; no local W suffix or governing P-type correlation certified. Number is neither historical instance ID nor installed quantity.

IMG_1332 · Locate on drawing ↗

Drawing notation: 200

Printed number beside station; no local W suffix or governing P-type correlation certified. Number is neither historical instance ID nor installed quantity.

lighting1013d-img1332-cod-delivery-row-station-02unreviewed · observed

luminaire_type_mapping

Unresolved

No governing fixture/P-type key verified in this bounded station crop; not evidence that no key survives elsewhere.

IMG_1332 · Locate on drawing ↗

No governing fixture/P-type key verified in this bounded station crop; not evidence that no key survives elsewhere.

lighting1013d-img1332-cod-delivery-rowverified · derived

drawn_regional_station_count

2 individually recorded plain circular outlet stations

2 count

Sum of the separately recorded drawn stations in this bounded group only. Excludes adjacent symbol families, routes and unreviewed stations; does not establish installed count.

IMG_1332 · Locate on drawing ↗

Drawing notation: 2 individually recorded plain circular outlet stations

Sum of the separately recorded drawn stations in this bounded group only. Excludes adjacent symbol families, routes and unreviewed stations; does not establish installed count.

Calculated from: lighting1013d-img1332-020-drawn_outlet_station_presence, lighting1013d-img1332-023-drawn_outlet_station_presence

lighting1013d-img1332-cod-delivery-rowverified · printed

printed_named_area_witness

C.O.D. DELIVERY

Printed named-area witness adjacent to bounded electrical row; no canonical room polygon or P-type assignment established.

IMG_1332 · Locate on drawing ↗

Drawing notation: C.O.D. DELIVERY

Printed named-area witness adjacent to bounded electrical row; no canonical room polygon or P-type assignment established.

services1014y-img1332-heating-note-assemblyverified · printed

radiator_tube_count_default

ALL RADIATORS ON THIS FLOOR TO BE 3 TUBE

3 count

Printed tube count per radiator under floor general rule; not installed quantity.

IMG_1332 · Locate on drawing ↗

Drawing notation: ALL RADIATORS ON THIS FLOOR TO BE 3 TUBE

Printed tube count per radiator under floor general rule; not installed quantity.

services1014y-img1332-heating-note-assemblyverified · printed

radiator_height_default

20″ HIGH UNLESS OTHERWISE NOTED

20 in

Explicit inch mark and unless-otherwise-noted qualification retained.

IMG_1332 · Locate on drawing ↗

Drawing notation: 20″ HIGH UNLESS OTHERWISE NOTED

Explicit inch mark and unless-otherwise-noted qualification retained.

services1014y-img1332-heating-note-assemblyverified · printed

radiator_connection_wall_relationship

ALL RADIATOR CONNECTIONS SHALL BE BROUGHT THRU WALL

Printed route requirement only; individual penetration positions and sizes remain unknown.

IMG_1332 · Locate on drawing ↗

Drawing notation: ALL RADIATOR CONNECTIONS SHALL BE BROUGHT THRU WALL

Printed route requirement only; individual penetration positions and sizes remain unknown.