Room 714 source-to-world placement gate
FAIL — W8 is the wrong floor and IMG_1221 context is provisionalW8 / IMG_1219 is the sixth-floor plan. Room 714 is on the seventh floor, so a direct IMG_0931-to-W8 fit would be a floor-category error. W8 may inform shared building axes only through existing project conventions; it cannot place Room 714 millwork. The existing Room 714 polygon has 3.25-foot conservative uncertainty and unreviewed finish faces. IMG_0931 supplies wall-specific millwork plans/elevations but no accepted common controls, no scale-bearing whole-room plan and no checked orientation correspondence.
North-wall elevation and adjacent north-wall plan strip, including the 6'-0" and 7'-6 5/8" controls and lettered detail callouts.
East-wall elevation with the printed instruction that the west wall is the same in reverse; repeated sliding-door/panel fields and lower panels.
South-wall elevation, two opening-like bays, fitted panel/casework fields, section A-A, and the 7'-0" opening-height control.
North, south, east and west wall plan strips and local member/track dimensions.