Printed values, calculations, image traces and observed counts are different kinds of evidence. “Verified” applies to the specific reading—not to the whole room or model.
mepnotes1014z-1340-underground-steam-detailverified · printed
culvert_material_designation
CONCRETE CULVERT PIPE - PLAINLegible material/designation fragment; preceding word not fully transcribed.
mepnotes1014z-1340-underground-steam-detailverified · printed
canvas_jacket_layer
CANVAS JACKETPrinted leader identifies canvas jacket around covered steam pipe; not a thickness.
mepnotes1014z-1340-underground-steam-detailverified · printed
pipe_support_material
APPROVED CAST IRON SADDLE GUIDE AND ROLLERUnderground service saddle/guide/roller clause, distinct from house-tank supports.
mepnotes1014z-1340-underground-steam-detailverified · printed
bedding_material
GRAVELLeader points to bedding beneath culvert; gradation and compaction unspecified.
mepnotes1014z-1340-underground-steam-detailillegible · printed
bedding_depth_unresolved
[vertical bedding dimension unreadable]Numeric value unresolved
Vertical bedding thickness glyph not reliably resolved; remains null.
mepnotes1014z-1340-boiler-trench-detailverified · printed
trench_internal_width
12″12 in
Printed horizontal inside-face dimension across trench.
mepnotes1014z-1340-boiler-trench-detailverified · printed
trench_internal_depth
12″12 in
Printed vertical dimension from upper interior datum to trench floor.
mepnotes1014z-1340-boiler-trench-detailillegible · printed
trench_base_thickness_unresolved
[vertical base thickness glyph unclear]Numeric value unresolved
Base thickness dimension is not confidently transcribed.
mepnotes1014z-1340-boiler-trench-detailverified · printed
cover_section_length_approx
SECTIONS ABOUT 3 FT. LONG3 ft
Approximate cover-section length; ABOUT retained. Not total trench length.
mepnotes1014z-1340-boiler-trench-detailverified · printed
cover_surface
GROOVED OR CHECKERED COVER PLATETwo permitted cover surface descriptions; no selection inferred.
mepnotes1014z-1340-boiler-trench-detailverified · printed
cover_material_options
TO BE CAST IRON OR ROLLED STEELPrinted alternative cover materials remain alternatives, not a selected material.
mepnotes1014z-1340-boiler-trench-detailverified · printed
curb_material
STOCK C.I. CURBC.I. designation retained for trench curb.
mepnotes1014z-1340-boiler-trench-detailverified · printed
anchor_spacing_approx
ANCHOR BOLTS ABOUT 24″ ON CENTERS24 in
Approximate anchor-bolt spacing only; diameter and count unresolved.
mepnotes1014z-1340-boiler-trench-detailverified · printed
roller_nominal_diameter
¾″ PIPE ROLLERS0.75 in
Nominal pipe designation for rollers, not verified outside diameter.
mepnotes1014z-1340-boiler-trench-detailverified · printed
roller_spacing
6″ APART6 in
Spacing in pipe-roller installation note.
mepnotes1014z-1340-boiler-trench-detailverified · printed
roller_embedment
SET 2″ INTO CONCRETE2 in
Embedment requirement from roller clause; endpoint geometry not independently traced.
mepnotes1014z-1340-boiler-trench-detailverified · printed
roller_projection
AND 1″ ABOVE TRENCH FLOOR1 in
Projection above trench floor in same roller clause.
mepnotes1014z-1340-boiler-trench-detailverified · printed
cement_finish
NEAT CEMENTFinish designation printed at trench lining; thickness unresolved.
mepnotes1014z-1340-boiler-trench-detailillegible · printed
cement_finish_thickness_unresolved
[fraction unclear] NEAT CEMENTNumeric value unresolved
Fraction before NEAT CEMENT not confidently transcribed.
mepnotes1014z-1340-oil-coil-detailverified · printed
coil_diameter
16″ DIAM.16 in
Horizontal arrow endpoints bracket coil at its upper turns; diameter is source-detail geometry, not tank diameter.
mepnotes1014z-1340-oil-coil-detailverified · printed
coil_detail_oil_tank_diameter
OIL TANK 9′-0″ DIA.9 ft
Vertical annotation beside oil-heating-coil detail supplies a distinct tank-diameter witness. Retain separately from 8′-0″ DIA. in fuel-oil-tank detail: target correspondence, endpoints and governing revision unresolved; no replacement or reconciliation.
IMG_1340 · W-PH460 · Locate on drawing ↗Drawing notation: OIL TANK 9′-0″ DIA.
Vertical annotation beside oil-heating-coil detail supplies a distinct tank-diameter witness. Retain separately from 8′-0″ DIA. in fuel-oil-tank detail: target correspondence, endpoints and governing revision unresolved; no replacement or reconciliation.
Conflicting readings: detail-1340o-tank-diameter
mepnotes1014z-1340-oil-coil-detailverified · printed
oil_return_nominal_diameter
1¼″ OIL RETURN1.25 in
Leader to upper-left oil-return stub; nominal size, not outside diameter or installed route.
mepnotes1014z-1340-oil-coil-detailverified · printed
return_nominal_diameter
1¼″ RETURN1.25 in
Separate lower-left return stub in oil-heating-coil detail. Service suffix retained exactly; no broader system connection inferred.
mepnotes1014z-1340-oil-coil-detailverified · printed
screen_designation
WIRE SCREENScreen annotation near lower return/suction details; mesh, metal and dimensions unresolved.
servicesched1013f-house-tank-section-aaillegible · printed
shell_fraction_still_illegible
[fraction unreadable] SHELLNumeric value unresolved
Native same original house-tank shell witness still illegible; no3/8 substitution.
IMG_1340 · Locate on drawing ↗Drawing notation: [fraction unreadable] SHELL
Native same original house-tank shell witness still illegible; no3/8 substitution.
servicesched1013f-house-tank-section-aaillegible · printed
head_fraction_still_illegible
[fraction unreadable] HEADSNumeric value unresolved
Native same original house-tank head witness still illegible; no1/2 substitution.
IMG_1340 · Locate on drawing ↗Drawing notation: [fraction unreadable] HEADS
Native same original house-tank head witness still illegible; no1/2 substitution.
plumbingwitness1014i-img1340-oil-heating-coilverified · printed
heating_coil_nominal_pipe_diameter
1½″ PIPE HEATING COIL1.5 in
Local leader nominal pipe size; no material/seamless fabrication asserted.
plumbingwitness1014i-img1340-oil-heating-coilverified · printed
steam_nominal_branch_diameter
1½″ STEAM1.5 in
Same original coil-top steam branch leader; not tank shell, apparatus OD or installed quantity.
IMG_1340 · Locate on drawing ↗Drawing notation: 1½″ STEAM
Same original coil-top steam branch leader; not tank shell, apparatus OD or installed quantity.
plumbingwitness1014i-img1340-oil-heating-coilverified · printed
spacing_chain_count
26 @ 3″ CENTERS = 6′-6″ APPROX26 count
Spacing-chain count, not installed coil/fixture quantity or developed pipe length.
IMG_1340 · Locate on drawing ↗Drawing notation: 26 @ 3″ CENTERS = 6′-6″ APPROX
Spacing-chain count, not installed coil/fixture quantity or developed pipe length.
plumbingwitness1014i-img1340-oil-heating-coilverified · printed
center_spacing
26 @ 3″ CENTERS = 6′-6″ APPROX3 in
Printed centers of coil spacing chain.
plumbingwitness1014i-img1340-oil-heating-coilverified · printed
spacing_chain_span
26 @ 3″ CENTERS = 6′-6″ APPROX6.5 ft
Printed6feet6inches as decimal feet; approximate qualifier retained, distinct from developed160ft reading.
IMG_1340 · Locate on drawing ↗Drawing notation: 26 @ 3″ CENTERS = 6′-6″ APPROX
Printed6feet6inches as decimal feet; approximate qualifier retained, distinct from developed160ft reading.
plumbingwitness1014i-img1340-oil-heating-coilunreviewed · observed
pipe_material_unestablished
1½″ PIPE HEATING COILExact PIPE noun does not supply material species or seamless fabrication. Earlier2″SEAMLESS locus still needs separate reconciliation.
IMG_1340 · Locate on drawing ↗Drawing notation: 1½″ PIPE HEATING COIL
Exact PIPE noun does not supply material species or seamless fabrication. Earlier2″SEAMLESS locus still needs separate reconciliation.
servicesched1013f-hot-water-tank-section-aaverified · printed
diameter
48″ DIA. × 6′-0″ HOT WATER TANK48 in
Apparatus diameter printed with DIA. label in section A-A hot-water-tank callout; not nominal pipe size or an asserted outside diameter convention.
IMG_1340 · Locate on drawing ↗Drawing notation: 48″ DIA. × 6′-0″ HOT WATER TANK
Apparatus diameter printed with DIA. label in section A-A hot-water-tank callout; not nominal pipe size or an asserted outside diameter convention.
Calculated from: servicesched1013f-img1340-033-apparatus_designation
servicesched1013f-hot-water-tank-section-aaverified · printed
length
48″ DIA. × 6′-0″ HOT WATER TANK6 ft
Source-local printed service property; no installed quantity, as-built state, accepted building coordinates or architectural approval.
IMG_1340 · Locate on drawing ↗Drawing notation: 48″ DIA. × 6′-0″ HOT WATER TANK
Source-local printed service property; no installed quantity, as-built state, accepted building coordinates or architectural approval.
Calculated from: servicesched1013f-img1340-033-apparatus_designation
servicesched1013f-economizer-section-aaverified · printed
diameter
48″ DIA. × 10′-0″ ECONOMIZER48 in
Apparatus diameter printed with DIA. label in section A-A economizer callout; not nominal pipe size or an asserted outside diameter convention.
IMG_1340 · Locate on drawing ↗Drawing notation: 48″ DIA. × 10′-0″ ECONOMIZER
Apparatus diameter printed with DIA. label in section A-A economizer callout; not nominal pipe size or an asserted outside diameter convention.
Calculated from: servicesched1013f-img1340-030-apparatus_designation
servicesched1013f-economizer-section-aaverified · printed
length
48″ DIA. × 10′-0″ ECONOMIZER10 ft
Source-local printed service property; no installed quantity, as-built state, accepted building coordinates or architectural approval.
IMG_1340 · Locate on drawing ↗Drawing notation: 48″ DIA. × 10′-0″ ECONOMIZER
Source-local printed service property; no installed quantity, as-built state, accepted building coordinates or architectural approval.
Calculated from: servicesched1013f-img1340-030-apparatus_designation
detail-1340o-fuel-oil-tankverified · printed
original_section_saddle_material
CAST IRON SADDLESPrinted fuel-oil-tank section support; distinct from house tank.
detail-1340o-fuel-oil-tankverified · observed
colored_section_support_annotation
STRUCTURAL STEELYellow support annotation retained as separate observed layer; not substituted for original supports.
IMG_1340 · Locate on drawing ↗Drawing notation: STRUCTURAL STEEL
Yellow support annotation retained as separate observed layer; not substituted for original supports.
servicesched1013f-house-tank-section-aaverified · printed
tank_designation
HOUSE TANKSource-local printed schedule/detail property only; no installed quantity, physical coordinates or architectural approval.
servicesched1013f-house-tank-section-aaverified · printed
diameter
64″ DIA.64 in
Source-local printed schedule/detail property only; no installed quantity, physical coordinates or architectural approval.