Gus J. SolomonUnited States Courthouse
← Back to the building1933 reconstruction · research preview

The measured building.

Every dimension belongs to an object and a drawing. Original room numbers, object marks, printed values and source regions stay together—even when the answer is unresolved.

Source photographs
464
Identified objects
5833
Verified printed values
15211
Disputed values
21

464 of 464 photographs have extraction records, containing 31,062 properties. Initial image review is not exhaustive extraction: 0 photographs have passed the full-region check. 66 numbered sheets are reconciled. Modeling and architectural registration are separate work; these counts do not establish a complete building.

Download the structured register (JSON)

Open the coordinated research model →

Clear filters
IMG_1328 · Folder 186

Basement & Foundation Plan

Original sheet identity has not yet been reconciled.

Extraction: Reviewed · extraction partial. Partial: 96 main footing rows, 34 stubs and 17 entrance instances transcribed. Ambiguous schedule cells and unregistered positions are not approved geometry. Four corner controls and six check intersections on each sheet; source orientation; existing 147-point trace set transformed arithmetically. Reuse of previously transcribed C4 footing/cap dimensions and bottom reference only. C24 pad schedule and placement gate; no accepted world pad box. C24 pad schedule and placement gate; no accepted world pad box. C24 pad schedule and placement gate; no accepted world pad box. C24 pad schedule and placement gate; no accepted world pad box. C24 pad schedule and placement gate; no accepted world pad box. C24 pad schedule and placement gate; no accepted world pad box. C24 pad schedule and placement gate; no accepted world pad box. C24 pad schedule and placement gate; no accepted world pad box. C24 pad schedule and placement gate; no accepted world pad box. C24 pad schedule and placement gate; no accepted world pad box. C24 pad schedule and placement gate; no accepted world pad box. C24 pad schedule and placement gate; no accepted world pad box. C24 pad schedule and placement gate; no accepted world pad box. C1 scheduled size and column control; signed pad-center offset unproved. C1 scheduled size and column control; signed pad-center offset unproved. C1 scheduled size and column control; signed pad-center offset unproved. C1 scheduled size and column control; signed pad-center offset unproved. C1 scheduled size and column control; signed pad-center offset unproved. C1 scheduled size and column control; signed pad-center offset unproved. C1 scheduled size and column control; signed pad-center offset unproved. C1 scheduled size and column control; signed pad-center offset unproved. C1 scheduled size and column control; signed pad-center offset unproved. C1 scheduled size and column control; signed pad-center offset unproved. C1 scheduled size and column control; signed pad-center offset unproved. C1 scheduled size and column control; signed pad-center offset unproved. C1 corner repick; scalar E established, signed pad placement still unresolved. C1 corner repick; scalar E established, signed pad placement still unresolved. C1 corner repick; scalar E established, signed pad placement still unresolved. C1 corner repick; scalar E established, signed pad placement still unresolved. C1 corner repick; scalar E established, signed pad placement still unresolved. C1 corner repick; scalar E established, signed pad placement still unresolved. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 pad schedule, one-axis center, signed-offset and elevation gate. C16 steel-column row repick; footing signed Z offset remains unresolved. C16 steel-column row repick; footing signed Z offset remains unresolved. C16 steel-column row repick; footing signed Z offset remains unresolved. C16 steel-column row repick; footing signed Z offset remains unresolved. C16 steel-column row repick; footing signed Z offset remains unresolved. C16 steel-column row repick; footing signed Z offset remains unresolved. C24 pad centerline/side-orientation gate; signed X/Z placement remains unresolved. C24 pad centerline/side-orientation gate; signed X/Z placement remains unresolved. C24 pad centerline/side-orientation gate; signed X/Z placement remains unresolved. C24 pad centerline/side-orientation gate; signed X/Z placement remains unresolved. C24 pad centerline/side-orientation gate; signed X/Z placement remains unresolved. C24 pad centerline/side-orientation gate; signed X/Z placement remains unresolved. C24 pad centerline/side-orientation gate; signed X/Z placement remains unresolved. C24 pad centerline/side-orientation gate; signed X/Z placement remains unresolved. C24 pad centerline/side-orientation gate; signed X/Z placement remains unresolved. C24 pad centerline/side-orientation gate; signed X/Z placement remains unresolved. C24 pad centerline/side-orientation gate; signed X/Z placement remains unresolved. C24 pad centerline/side-orientation gate; signed X/Z placement remains unresolved. C24 pad centerline/side-orientation gate; signed X/Z placement remains unresolved. C24 pad centerline/side-orientation gate; signed X/Z placement remains unresolved. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. C13–C15 pad schedule and placement gate; finite world pads withheld. Partial timed visual review: Prior-package and OCR audit only; no new image inspection or duplicate verified readings. Partial timed visual review: Text/OCR and prior-package audit only; no new image inspection and no duplicate verified measurements. Partial timed visual review: Prior evidence reused; only selected remaining source-local regions reviewed. No historical placement or accepted physical geometry. Partial timed visual review: undefined Partial timed visual review: undefined Partial timed visual review: undefined Partial timed visual review: undefined Partial timed visual review: undefined Partial timed visual review: undefined Partial timed visual review: Zero-image coverage routing. No new visual area or source-reading promotion. Partial timed visual review: undefined

Hide coordinated geometry overlay →
Registration: provisional · 6 independent checks · maximum residual 0.458 ft.

Unresolved extraction work
  • main-1-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-1-rebar-count: First digit is not secure; the diameter reads 7/8 inch.
  • main-4-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-4-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-5-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-5-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-6-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-6-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-7-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-7-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-8-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-8-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-9-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-9-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-10-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-10-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-11-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-11-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-12-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-13-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-13-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-14-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-15-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-16-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-16-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-18-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-19-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-20-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-20-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-21-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-22-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-23-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-24-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-24-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-25-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-25-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-26-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-26-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-27-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-27-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-28-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-30-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-33-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-35-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-36-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-36-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-37-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-37-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-42-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-42-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-43-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-43-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-44-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-45-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-46-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-47-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-48-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-49-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-51-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-52-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-52-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-53-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-53-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-54-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-57-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-58-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-58-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-59-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-59-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-60-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-61-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-62-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-63-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-64-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-65-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-66-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-67-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-68-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-69-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-70-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-70-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-71-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-71-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-72-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-72-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-73-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-73-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-74-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-75-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-76-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-77-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-78-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-79-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-80-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-81-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-82-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-83-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-84-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-84-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-85-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-86-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-86-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-87-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-87-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-88-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-88-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-89-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-89-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-90-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-90-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-91-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-91-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-92-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-92-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-93-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-93-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-94-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-94-rebar: Printed ditto refers to an unresolved reinforcement cell.
  • main-95-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-95-rebar: Two-line transverse/longitudinal bar counts and/or diameters remain illegible.
  • main-96-cap-depth: Whole-foot/inch prefix transcribed; small fractional-inch ending is not reliable in this photograph.
  • main-13-bottom-elevation: Elevation label is too small or overlaps other drafting.
  • main-17-bottom-elevation: Elevation label is too small or overlaps other drafting.
  • main-23-bottom-elevation: Elevation label is too small or overlaps other drafting.
  • stub-S8-bottom-elevation: Elevation label is too small or overlaps other drafting.
  • boiler-room-floor-elevation: Small 2/7 glyph is ambiguous. Cross-sheet evidence supplied by the envelope extraction reads 77.25.
  • oil-tank-foundation-thickness-rebar: Small vertical lettering is not reliable at this photograph's resolution.
  • entrance-row-spacing: 0/1 ending is ambiguous in the available crop.
  • drawing-number: The right portion of the title block is occluded by the photograph edge/wooden strip. A later correspondence report mentions 414/400, but that is not treated as the sheet's visible number.
  • small-plan-auxiliary-dimensions: The bounded crop pass does not exhaust every small measured value in these dense areas. No exhaustive-completion claim is made.
  • main-78-79-handwritten-revisions: Yellow handwriting appears adjacent to both printed depths. Its sign, date and revision authority are not established, so printed depths are retained without silently applying the annotation.
  • corner-offset-review: Current visual reading is 1½″ but the compact fraction needs a sharper source. Do not apply globally.
  • Resolve local residuals with a flatter scan or additional constrained registration before tighter geometric use.
  • Independently recheck each of 147 source symbol centers; this pass visually refines only registration controls and checks.
  • Resolve each footing/cap center from eccentricity and offset evidence before placing foundation solids.
  • Review remaining regions and companion details before claiming complete extraction.
  • C4 plan symbol and eccentricity direction
  • C4 footing detailed section and reinforcement
  • Cap thickness fraction
  • W409 suffix a E magnitude independently read and tied to C1
  • signed footing-center minus C1-column-center X offset
  • signed footing-center minus C1-column-center Z offset
  • independent check of actual C1 pad center and two footprint edges
  • cap/pier center, depth, and bearing transform
  • reinforcement quantity and detailed geometry
  • material/finish confirmation and as-built position
  • signed C1 pad-center minus steel-column-center X offset
  • signed C1 pad-center minus steel-column-center Z offset
  • which axis, if any, receives W409 E at the corner and whether a separate corner-axis offset applies
  • two independently identified and dimensioned C1 pad edges
  • cap/pier transform and bearing continuity
  • reinforcement layout and quantities
  • material and finish confirmation
  • as-built position
  • C16 world Z center and eccentricity
  • Physical world footprint
  • signed footing C.G. minus C16 steel-column center in world Z, including an explicit zero if applicable
  • dimensioned north and south pad edges relative to the C16 centerline or an attributable center-offset detail
  • cap center, orientation, thickness and bearing transform
  • reinforcement count and bar placement
  • independent/as-built check
  • actual-plan attribution of the Broadway footing centerline to C24 pad center of gravity
  • signed C24 pad-center minus steel-column-center X offset
  • signed C24 pad-center minus steel-column-center Z offset, including proof of zero if centered
  • 12-foot versus 14-foot scheduled side assignment to world X/Z from attributable pad edges or printed dimensions
  • cap, base, reinforcement and as-built geometry
  • C13 pad C.G. minus steel center signed X offset, including its side orientation
  • legible C13 footing-bottom elevation
  • cap center, thickness and bearing transform
  • printed C14 steel-column world X station or checked dimensioned tie
  • C14 pad C.G. minus steel center signed X and Z offsets, including proof of zero on either axis
  • applicable eccentricity key or direct pad-center control
  • printed C15 steel-column world X station or checked dimensioned tie
  • C15 pad C.G. minus steel center signed X and Z offsets, including proof of zero on either axis
  • Remaining member, reinforcement and connection dimensions require fine-region review
  • Revision marks and historical instance placements remain unreconciled
  • Companion-sheet registration and modeling checks remain outstanding
  • Complete fine-fraction/member schedule transcription
  • Historical instance mapping and endpoint registration
  • Annotated revisions and companion notes reconciliation
  • Accepted connections and modeling checks
  • Complete member/plate/bar fraction transcription
  • Historical instance and source-to-plan registration
  • Revision authority and companion applicability
  • Connection and modeling acceptance checks
  • Historical issue, revision authority and actual installation remain unresolved.
  • Accepted architectural registration, host faces, physical routes and installed quantities remain unresolved.
  • Materials, finishes, fixture type mappings, physical dimensions and mounting heights remain unknown.
  • Unvisited sheet regions, notes, schedules, callouts and companion details require review; extraction partial and modeling/checking unchecked.
  • All other notes, regions, schedules and companion details remain partially reviewed; this package grants no architectural acceptance.
  • Old failed fractions, unsupported units, broad placement gates and previously resolved questions were not re-viewed or promoted.
  • Boiler-room slab candidate remains unreviewed; no confirmation or datum selection.
  • Installed instance locations, source-to-plan registration, governing original/revision applicability and as-built correspondence remain unresolved.
  • Material grades, finishes, full dimensional envelopes, capacities and independent model checks remain unresolved.
  • Other regions, notes, schedules and companion details require review; this is partial extraction and grants no geometry approval.
  • Rows87 and95 have unequal transverse/longitudinal counts. Their historical countEachWay nulls remain open because the field cannot represent unequal directional counts.
  • Bar diameter fractions/units and cap thickness fractions remain unresolved; no pile/cap topology, signed C.G. placement or world coordinates inferred.
  • Complete source-to-instance registration, physical endpoints, installed quantities and revision authority remain unresolved.
  • Unreviewed regions, companion sheets, schedules and fine fractions remain open; this package is not exhaustive coverage.
  • Material grades, connection capacities, world transforms and independent model/as-built checks remain unestablished.
  • Typical-detail exceptions and dimension-witness line are source-local only; no footing C.G. world location established.
  • One crop intended for trenches actually showed schedule rows1–28; counted as a wrong-target attempt, no new reinforcement or cap-fraction reading adopted. No piles or lateral system inferred.
  • Complete source-to-instance and endpoint registration remains unresolved.
  • Material grades, finishes, connection capacities and as-built checks remain unestablished.
  • Unreviewed regions, fine fractions, schedules, companion applicability and revision authority remain open.
  • Bounded rows 87 and 95 reinspection did not independently resolve cap-thickness fractions or reinforcement diameter fraction/units; prior directional counts reused.
  • No countEachWay closure because transverse and longitudinal quantities differ; no pile/cap topology or world placement inferred.
  • Full source-to-instance assignment, physical endpoints, installed quantities and governing revision remain unresolved.
  • Unreviewed regions, notes, fine fractions and companion sheets remain open; this package is not exhaustive coverage.
  • No world geometry, material grade, structural capacity or model acceptance established.
  • Installed instances, physical endpoints, source-to-plan registration and governing original/revision applicability remain unresolved.
  • Complete member dimensions, reinforcement profiles, material grades, connection capacities and as-built/model checks remain outstanding.
  • Retain every routing entry and prior inventory missing property. Pending selector excludes already closed questions but is not exhaustive region coverage.
  • Original/revision authority, companion applicability, source-to-instance mapping, physical endpoints, material/finish, independent model/as-built check remain separate.
  • No whole-source completion, accepted geometry or irrecoverable-gap claim.

Download OCR observations (unverified)

Loading the selected drawing…

Scroll or pinch to inspect this drawing. Blue: printed controls. Gold: provisional geometry. Pink: held-out check residuals. An overlay is a comparison, not certification. Archival drawing photograph · Oregon Historical Society research collections.

Open source image separately ↗

2049 matching properties

Printed values, calculations, image traces and observed counts are different kinds of evidence. “Verified” applies to the specific reading—not to the whole room or model.

column-E-A2unreviewed · traced

world x foundation trace

-9.861430478806673 ft (provisional trace)

-9.86143 ft · estimated uncertainty ±1.927470103 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-A2unreviewed · traced

world z foundation trace

87.503559043093 ft (provisional trace)

87.503559 ft · estimated uncertainty ±1.927470103 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-A3unreviewed · traced

world x foundation trace

0.1190597792213026 ft (provisional trace)

0.11906 ft · estimated uncertainty ±1.926817414 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-A3unreviewed · traced

world z foundation trace

87.50679133151034 ft (provisional trace)

87.506791 ft · estimated uncertainty ±1.926817414 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-A4unreviewed · traced

world x foundation trace

10.077530904125043 ft (provisional trace)

10.077531 ft · estimated uncertainty ±1.92603085 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-A4unreviewed · traced

world z foundation trace

87.57857259445352 ft (provisional trace)

87.578573 ft · estimated uncertainty ±1.92603085 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-A5unreviewed · traced

world x foundation trace

20.162782634571933 ft (provisional trace)

20.162783 ft · estimated uncertainty ±1.925588868 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-A5unreviewed · traced

world z foundation trace

87.44043607424713 ft (provisional trace)

87.440436 ft · estimated uncertainty ±1.925588868 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-B1unreviewed · traced

world x foundation trace

-19.876535351463655 ft (provisional trace)

-19.876535 ft · estimated uncertainty ±1.911161441 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-B1unreviewed · traced

world z foundation trace

97.14004403716135 ft (provisional trace)

97.140044 ft · estimated uncertainty ±1.911161441 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-B2unreviewed · traced

world x foundation trace

-10.042411875613775 ft (provisional trace)

-10.042412 ft · estimated uncertainty ±1.910755417 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-B2unreviewed · traced

world z foundation trace

97.02981859540385 ft (provisional trace)

97.029819 ft · estimated uncertainty ±1.910755417 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-B3unreviewed · traced

world x foundation trace

-0.1552127775946938 ft (provisional trace)

-0.155213 ft · estimated uncertainty ±1.909968744 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-B3unreviewed · traced

world z foundation trace

97.12639612432316 ft (provisional trace)

97.126396 ft · estimated uncertainty ±1.909968744 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-B4unreviewed · traced

world x foundation trace

9.926595123809737 ft (provisional trace)

9.926595 ft · estimated uncertainty ±1.909388543 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-B4unreviewed · traced

world z foundation trace

97.08928833336384 ft (provisional trace)

97.089288 ft · estimated uncertainty ±1.909388543 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-B5unreviewed · traced

world x foundation trace

19.91696208770283 ft (provisional trace)

19.916962 ft · estimated uncertainty ±1.908806859 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-B5unreviewed · traced

world z foundation trace

97.04755401892936 ft (provisional trace)

97.047554 ft · estimated uncertainty ±1.908806859 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-C1unreviewed · traced

world x foundation trace

-29.7293972565108 ft (provisional trace)

-29.729397 ft · estimated uncertainty ±1.891498701 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-C1unreviewed · traced

world z foundation trace

108.69448206008049 ft (provisional trace)

108.694482 ft · estimated uncertainty ±1.891498701 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-C2unreviewed · traced

world x foundation trace

-19.577332556283963 ft (provisional trace)

-19.577333 ft · estimated uncertainty ±1.891971825 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-C2unreviewed · traced

world z foundation trace

108.09463162773555 ft (provisional trace)

108.094632 ft · estimated uncertainty ±1.891971825 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-C3unreviewed · traced

world x foundation trace

-9.645191704619059 ft (provisional trace)

-9.645192 ft · estimated uncertainty ±1.893051538 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-C3unreviewed · traced

world z foundation trace

107.14354590477974 ft (provisional trace)

107.143546 ft · estimated uncertainty ±1.893051538 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-C4unreviewed · traced

world x foundation trace

0.28669628572651945 ft (provisional trace)

0.286696 ft · estimated uncertainty ±1.894246151 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-C4unreviewed · traced

world z foundation trace

106.11541237609795 ft (provisional trace)

106.115412 ft · estimated uncertainty ±1.894246151 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-C5unreviewed · traced

world x foundation trace

10.075996788712272 ft (provisional trace)

10.075997 ft · estimated uncertainty ±1.895455446 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-C5unreviewed · traced

world z foundation trace

105.07282381919126 ft (provisional trace)

105.072824 ft · estimated uncertainty ±1.895455446 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-C6unreviewed · traced

world x foundation trace

20.154516769320328 ft (provisional trace)

20.154517 ft · estimated uncertainty ±1.896866737 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-C6unreviewed · traced

world z foundation trace

103.89254515460459 ft (provisional trace)

103.892545 ft · estimated uncertainty ±1.896866737 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-C7unreviewed · traced

world x foundation trace

30.38415229224251 ft (provisional trace)

30.384152 ft · estimated uncertainty ±1.898379281 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

column-E-C7unreviewed · traced

world z foundation trace

102.63667561081061 ft (provisional trace)

102.636676 ft · estimated uncertainty ±1.898379281 ft

Candidate support-center location; the prior trace may represent a steel column, concrete pilaster, stub, or entrance support. Member material/type requires the original schedule.

b-enclosed-floor-outlineverified · printed

floor-datum

FIN.BASEMENT FL.,EL.80.25

80.25 ft

General basement reference, with regional exceptions.

IMG_1328 · Locate on drawing ↗

Drawing notation: FIN.BASEMENT FL.,EL.80.25

Existing foundation extraction, referenced without reopening.

foundation-main-6-padverified · printed

footing.scheduleWidth

6; 12′6″ wide × 2′2″; cap 7′4″ × 8′4″ × 1′4[?]″

150 in

Width-only schedule cell; this is not a 12′6″ square. Source audit state: checked-master-crop-single-reader.

IMG_1328 · Locate on drawing ↗

Drawing notation: 6; 12′6″ wide × 2′2″; cap 7′4″ × 8′4″ × 1′4[?]″

Calculated from: foundation-main-6-footing-widthInches

foundation-main-6-padillegible · printed

footing.scheduleLength

6; 12′6″ wide × 2′2″; cap 7′4″ × 8′4″ × 1′4[?]″

Numeric value unresolved

Longitudinal length is not stated in this schedule row. Source audit state: unresolved.

IMG_1328 · Locate on drawing ↗

Drawing notation: 6; 12′6″ wide × 2′2″; cap 7′4″ × 8′4″ × 1′4[?]″

Calculated from: foundation-main-6-footing-lengthInches

foundation-main-6-padverified · observed

footprint.stripRunAngleFromWorldX

6; (-9′0″); strip edges run along Madison; longitudinal break lines

0 deg

The strip's longitudinal edges run parallel to Madison/world X. This establishes run direction, not a numeric longitudinal extent. Source audit state: checked-master-crop-single-reader.

IMG_1328 · Locate on drawing ↗

Drawing notation: 6; (-9′0″); strip edges run along Madison; longitudinal break lines

foundation-main-6-padverified · observed

footprint.widthAxisAngleFromWorldX

6; (-9′0″); strip edges run along Madison; longitudinal break lines; 6; 12′6″ wide × 2′2″; cap 7′4″ × 8′4″ × 1′4[?]″

90 deg

The scheduled width crosses the strip along world Z. Source audit state: checked-master-crop-single-reader.

IMG_1328 · Locate on drawing ↗

Drawing notation: 6; (-9′0″); strip edges run along Madison; longitudinal break lines

IMG_1328 · Locate on drawing ↗

Drawing notation: 6; 12′6″ wide × 2′2″; cap 7′4″ × 8′4″ × 1′4[?]″

Calculated from: footing-6-placement-strip-run-axis

foundation-main-6-padverified · derived

footprint.worldZSpan

6; 12′6″ wide × 2′2″; cap 7′4″ × 8′4″ × 1′4[?]″; 6; (-9′0″); strip edges run along Madison; longitudinal break lines

12.5 ft

Source audit state: checked-arithmetic-from-source-linked-parents.

IMG_1328 · Locate on drawing ↗

Drawing notation: 6; 12′6″ wide × 2′2″; cap 7′4″ × 8′4″ × 1′4[?]″

IMG_1328 · Locate on drawing ↗

Drawing notation: 6; (-9′0″); strip edges run along Madison; longitudinal break lines

Calculated from: footing-6-placement-schedule-width, footing-6-placement-width-axis

foundation-main-6-padillegible · observed

footprint.worldXSpan

6; (-9′0″); strip edges run along Madison; longitudinal break lines; 6; 12′6″ wide × 2′2″; cap 7′4″ × 8′4″ × 1′4[?]″

Numeric value unresolved

No numeric end/step location or longitudinal length was identified. Column bay dimensions are not footing end dimensions. Source audit state: unresolved.

IMG_1328 · Locate on drawing ↗

Drawing notation: 6; (-9′0″); strip edges run along Madison; longitudinal break lines

IMG_1328 · Locate on drawing ↗

Drawing notation: 6; 12′6″ wide × 2′2″; cap 7′4″ × 8′4″ × 1′4[?]″

Calculated from: footing-6-placement-schedule-length

foundation-main-6-padillegible · observed

footprint.longAxisAngleFromWorldX

6; (-9′0″); strip edges run along Madison; longitudinal break lines; 6; 12′6″ wide × 2′2″; cap 7′4″ × 8′4″ × 1′4[?]″

Numeric value unresolved

Strip run is X, but an individual segment's longest side is not asserted while its X length is unknown. Source audit state: unresolved.

IMG_1328 · Locate on drawing ↗

Drawing notation: 6; (-9′0″); strip edges run along Madison; longitudinal break lines

IMG_1328 · Locate on drawing ↗

Drawing notation: 6; 12′6″ wide × 2′2″; cap 7′4″ × 8′4″ × 1′4[?]″

Calculated from: footing-6-placement-span-x, footing-6-placement-span-z

View all source photographs →