Gus J. SolomonUnited States Courthouse
← Back to the building1933 reconstruction · research preview

The measured building.

Every dimension belongs to an object and a drawing. Original room numbers, object marks, printed values and source regions stay together—even when the answer is unresolved.

Source photographs
464
Identified objects
4872
Verified printed values
12046
Disputed values
20

464 of 464 photographs have extraction records, containing 27,517 properties. Initial image review is not exhaustive extraction: 0 photographs have passed the full-region check. 66 numbered sheets are reconciled. Modeling and architectural registration are separate work; these counts do not establish a complete building.

Download the structured register (JSON)

Open the coordinated research model →

Clear filters
IMG_1126 · Folder 191

DETAIL OF ELEVATOR #1 & TYPICAL DETAILS OF ELEVATOR ENCLOSURES

Sheet W229

Extraction: Reviewed · extraction partial. Bounded first-floor elevator audit: DETAIL OF ELEVATOR #1 & TYPICAL DETAILS OF ELEVATOR ENCLOSURES. First-floor Elevator No. 1 plan, column marks, axis order, clear-hatch labels and local offset witnesses. Elevator detail-to-W3 physical-placement gate: DETAIL OF ELEVATOR #1 & TYPICAL DETAILS OF ELEVATOR ENCLOSURES. W229 first-floor Elevator 1 enclosure and clear hatch: classification of the 2'-0 1/4" horizontal witness between the west outside enclosure face and Column 74 centerline, plus the 4'-0" vertical witness from Column 71 centerline to the south clear-hatch edge and the resulting 10'-0" north-south clear-hatch edge pair. Partial entrance-registration review: Targeted review confirms that the first-floor landing entrance is on the page-top/south enclosure face and runs in the W229 local-u direction, which the accepted symbolic column frame maps to building +X west/Broadway. The crop does not establish wall thickness or a physical face offset. Bounded W229 seventh-floor review of the Elevator No. 1 east-west outside-enclosure dimension chain on the Column 73-74 row. Elevator-front bounded gate: Elevator 1 south landing face direction and one-axis enclosure/hatch controls. Elevator No. 1 first-floor cross-sheet physical placement gate; one-axis controls only. Elevator No. 1 first-floor cross-sheet physical placement gate; one-axis controls only. Elevator No. 1 first-floor cross-sheet physical placement gate; one-axis controls only. Elevator No. 1 first-floor cross-sheet physical placement gate; one-axis controls only. Elevator No. 1 first-floor cross-sheet physical placement gate; one-axis controls only. Elevator No. 1 first-floor cross-sheet physical placement gate; one-axis controls only. Elevator No. 1 first-floor cross-sheet physical placement gate; one-axis controls only. Elevator No. 1 first-floor cross-sheet physical placement gate; one-axis controls only. Elevator No. 1 first-floor cross-sheet physical placement gate; one-axis controls only. Elevator No. 1 first-floor cross-sheet physical placement gate; one-axis controls only. Elevator No. 1 first-floor cross-sheet physical placement gate; one-axis controls only. Elevator No. 1 first-floor cross-sheet physical placement gate; one-axis controls only. Elevator No. 1 first-floor cross-sheet physical placement gate; one-axis controls only. Partial timed visual review: OCR, queue and existing extraction packages searched first. One sequential upright WebP inspection; only additive selected properties recorded. Previously verified readings reused without duplication. No complete extraction or accepted geometry. Partial timed visual review: OCR and existing text packages searched before one sequential upright WebP inspection. Additive region review; existing verified properties reused, not copied. No accepted geometry or cross-floor connection. Partial timed visual review: Text-first additive targeted review. Upright access-image coordinates; crops retain upright orientation. Source-local components only; existing verified records reused, not copied. Full image extraction remains incomplete. Partial timed visual review: Targeted additive review. Master crops preserve upright orientation and regions reference the full upright access image. Source-local head profile only; dimensions do not establish an installed opening or geometry. Earlier trap and jamb readings retained in their packages. Partial timed visual review: Selected original photographic layer; no revision authority or installed geometry accepted. Partial timed visual review: undefined Partial timed visual review: undefined Partial timed visual review: undefined Partial timed visual review: Source-local detail/region evidence only. Printed type/floor applicability does not establish installed occurrences.

Highlighted reading: 3/16″ STEEL NICKEL PLATE & BUCK. Fraction belongs to later head plate-and-buck leader; original photographic layer only. Does not establish alloy, nickel process, installed thickness or applicability beyond the separate printed caption.

Show every recorded property on this drawing →

Unresolved extraction work
  • Accepted world wall faces and exact shaft polygons for all three elevators
  • Registered relationship between W229/W230/W231 detail coordinates and W3 world coordinates
  • Rough-versus-finished enclosure wall planes and wall thicknesses
  • W217 title-block confirmation and exact endpoint interpretation for the 3'-6" and 6'-9 3/4" door readings
  • Exact first-floor Elevator 3 door width, height, jamb/head/sill and rough opening
  • Readable Elevator 3 vertical hatch/shaft witness
  • Car/cab/platform sizes, rail/counterweight coordinates, pit depths and overhead clearances
  • Accepted ramp length, slope and threshold build-up at Elevator 3
  • Architecturally accepted reconciliation of all floor traces, especially the fourth-floor mechanical underlay
  • Offset witness endpoints and exact hatch-to-axis coordinates remain unresolved.
  • For W229, the west outside enclosure face is fixed at world X = -65.020833 ft and the south/north clear-hatch edges are fixed at world Z = 46/56 ft; both clear-hatch world-X edges remain unresolved. For W230, the east outside enclosure face is fixed at X = 65.020833 ft and the clear-hatch east/west edges at X = 66.083333/73.083333 ft; both clear-hatch world-Z edges remain unresolved. Both elevators still lack finite enclosure-face endpoints, opposite faces, wall thickness and complete hatch-to-wall construction.
  • For W231, an exact non-collinear column/grid frame and a complete, classified shaft or clear-hatch width/depth chain.
  • Rough-face versus finish-face classification and wall thickness for each enclosure side.
  • Independently accepted matching W3 hatch or shaft faces and a reported hold-out corner residual.
  • Pit depth, overhead, slab opening and cross-floor continuation evidence for each elevator independently.
  • World wall plane and jamb-center/inside-jamb offsets for all three entrances.
  • Operating clear width and height, rough opening, leaf overlap/travel, sill, head and wall-thickness build-up.
  • Elevator 3 first-floor entrance dimensions and endpoint classes.
  • An independent check tying each local door centerline to the corresponding W3 landing wall.
  • Cab-to-hatch origin, platform size and inside-clear dimensions.
  • Guide-rail, counterweight and bracket centerlines tied to classified hatch faces.
  • Confirmed assignment of W219 Cab E elevations to Elevator 1, 2 or 3.
  • Door operator, travel/pocket and emergency-exit geometry.
  • Dimensioned horizontal extents and wall-face endpoints for the Elevator 1 vestibule and Elevator 2 Broadway foyer thresholds.
  • Elevator 3 ramp length, slope, threshold build-up and exact landing boundary at EL. 93.25 and EL. 95.33.
  • Registered sill/head coordinates and independent correspondence to W3 landing traces.
  • As-built confirmation before accepting vertical shaft or landing continuity.
  • North and south endpoints of the accepted face
  • Enclosure wall thickness and opposite wall face
  • World X coordinates of the 7-foot clear-hatch edges and their relationship to the accepted outside face
  • Vertical extent, floor/pit/overhead continuation and as-built correspondence
  • Complete physical shaft, door, cab and landing transforms
  • Accepted physical host-wall face and thickness
  • Exact entrance depth relative to the W229 clear-hatch edge
  • Rough opening and operating clear width/height
  • Jamb, reveal, frame, sill, threshold and door-leaf construction
  • Complete shaft, cab, guide, pit, overhead and machinery transforms
  • Independent as-built check
  • Printed or independently checked relation between W229 outside enclosure faces and W235 clear-plan faces
  • Accepted north-south outside and clear-face controls on the seventh floor
  • Masonry wall thickness, finish build-up and opening construction
  • Slab opening, pit, overhead, cab, guide rails, brackets and machinery
  • Held-out corresponding-face checks across W229, W235 and the seventh-floor architectural plan
  • A readable first-floor W217 Section E or applicable companion section with front and back faces and exact profile/depth dimensions for one named component, plus complete width and height endpoints for that same component.
  • Printed or independently checked panel extents before any ornament panels are given physical sizes; retain panel instances without fabricated dimensions until then.
  • Classified first-floor host wall face, thickness and jamb/reveal/sill/head interfaces tied to named W229 or W230 controls and the corresponding W3 wall or Bay P station.
  • An independent corresponding-face or endpoint residual within a stated tolerance for the chosen physical front, preserving conflicts and W3 trace uncertainty separately.
  • Complete fine dimension chains and classified rough/finish endpoints
  • Member profiles, fasteners, fabrication details and material-code reconciliation
  • Historical instance and floor-plan registration
  • Companion details, revision authority and independent physical connection checks
  • Right-side head/jamb/sill and tel trap door fine callouts need high-resolution crops; no numeric fabrication reading accepted.
  • Fine fractions and full dimension chains remain partially unreviewed
  • Endpoint classification and companion detail reconciliation
  • Source-to-building instance registration and accepted connections
  • Exact profile and thickness fractions
  • Fastener size, material and anchorage
  • Installed instance and floor registration
  • Companion revision authority and physical connection checks
  • All remaining regions and fabrication notes
  • Installed head and opening registration
  • Trap plate thickness and frame angle size
  • Later-detail plate fraction
  • Fasteners and anchorage
  • Companion revision authority
  • Installed occurrence, room identity and source-to-building registration
  • Original/revision authority and as-built correspondence
  • Complete member profiles, fixing stations and quantities
  • Architectural acceptance and physical geometry remain withheld
  • Main floor-plan matrix and section/title/table not reopened
  • All-region review remains incomplete
  • Trap plate thickness, frame angle components and countersunk fixing remain illegible in this exposure. Plan matrix and installation/world controls not re-reviewed.
  • Complete fine dimensions, profiles, materials, finishes, gauges and fastener schedules remain partial.
  • Installed quantities, room/storey allocation, governing revision and companion applicability remain unresolved.
  • Source-to-building transforms, rough/finish endpoint classes, complete openings and independent physical checks remain outstanding; authoring is withheld.
  • Trap checker-plate thickness, angle components and countersunk fixings remain unresolved. Lower plans, sill/jamb chains, equipment/beam schedule and installation/world controls remain partial.
  • Complete fine profiles, member sizes, fasteners, finish extents and endpoint classes remain partial.
  • Installed quantities, stair/storey/room assignment, closed openings, headroom, source-to-building registration and independent physical checks remain unresolved.
  • Governing original/revision and companion applicability remain unresolved; source reading does not approve geometry.
  • Complete member/profile dimensions, material/gauge/fastener schedules and exact endpoint classes
  • Installed stair/storey/room allocation, quantities, original/revision authority and companion applicability
  • Source-to-building registration, complete landing/shaft openings, independent physical checks and architectural acceptance
  • Checker plate thickness and frame angle3 components still unclear; countersunk fixing text needs finer companion witness
  • Remaining fine fractions, complete member profiles, fastener sizes/materials and finish extents require targeted source review.
  • Installed room/floor identity, exact rough/finish/cab/rail endpoints and companion registration remain unresolved.
  • Source-to-building transform, installed quantities, independent physical connections and architectural acceptance remain withheld.
  • Only right-side upper detail crop inspected; full plan matrix, machine-room/shaft sections and title/material table not visually revisited.
  • Trap checker-plate thickness, angle fractions and countersunk fixing text remain unresolved.
  • Nickel-steel plate thickness and exact lower jamb/sill/anchor chain remain open.

Download OCR observations (unverified)

Loading the selected drawing…

Scroll or pinch to inspect this drawing. The gold outline locates the selected reading. Archival drawing photograph · Oregon Historical Society research collections.

Open source image separately ↗

1 matching properties

Printed values, calculations, image traces and observed counts are different kinds of evidence. “Verified” applies to the specific reading—not to the whole room or model.

door-img1126-later-head-jambverified · printed

later_head_nickel_steel_plate_thickness_resolution

3/16″ STEEL NICKEL PLATE & BUCK

0.1875 in

Fraction belongs to later head plate-and-buck leader; original photographic layer only. Does not establish alloy, nickel process, installed thickness or applicability beyond the separate printed caption.

IMG_1126 · W-229 · Locate on drawing ↗

Drawing notation: 3/16″ STEEL NICKEL PLATE & BUCK

Fraction belongs to later head plate-and-buck leader; original photographic layer only. Does not establish alloy, nickel process, installed thickness or applicability beyond the separate printed caption.

Calculated from: door-20261012p-1126-m007

View all source photographs →